3
INITIAL CHECKING
OF THE BOILER. - TECHNICIAN.
To commission the boiler:
- ensure that the declaration of conformity of
installation is supplied with the appliance;
- ensure that the type of gas used corresponds to
boiler settings;
- check connection to a 230V-50Hz power mains,
correct L-N polarity and the earthing connec-
tion;
- make sure the heating system is filled with water
and that the manometer indicates a pressure of
1÷1.2 bar;
- make sure the air valve cap is open and that the
system is well deaerated;
- switch the boiler on and ensure correct igni-
tion;
- make sure the gas maximum, medium and mini-
mum flow rate and pressure values correspond to
those given in the handbook (Paragraph 3.17);
- check activation of the safety device in the event
of no gas, as well as the relative activation time;
- check activation of the main switch located
upstream from the boiler;
- check that the intake and/or exhaust terminals
are not blocked;
- check activation of the "no air" safety pressure
switch;
- ensure activation of all adjustment devices;
- seal the gas flow rate regulation devices (if set-
tings are modified);
- ensure production of domestic hot water;
- ensure sealing efficiency of water circuits;
- check ventilation and/or aeration of the instal-
lation room where provided.
If any checks/inspection relative to safety give
negative results, do not start the system.
SK
3
POČIATOČNÁ KONTROLA
KOTLA. - TECHNIK.
Počas uvádzania kotla do prevádzky je nutné:
- skontrolovať prítomnosť prehlásenia o zhode
danej inštalácie;
- skontrolovať, či použitý plyn odpovedá tomu,
pre ktorý je kotol určený;
- skontrolovať pripojenie k sieti 230V-50Hz,
správnosť polarity L-N a uzemnenia;
- skontrolovať, či je vykurovací systém naplnený
vodou podľa ručičky na manometre, ktorý má
ukazovať tlak 1÷1,2 bar;
- skontrolovať, či je klobúčik odvzdušňovacieho
ventilu otvorený a či je zariadenie dobre
odvzdušnené;
- zapnúť kotol a skontrolovať správnosť zapále-
nia;
- skontrolovať, či maximálny, stredný a minimálny
prietok plynu a príslušné hodnoty tlaku sú v súla-
de s hodnotami uvedenými v príručke (Odstavec
3.17);
- skontrolovať, či bezpečnostné zariadenia pre
prípad výpadku plynu pracuje správne a dobu,
za ktorú zasiahne;
- skontrolovať funkciu hlavného spínača umie-
steného v kotli;
- skontrolovať, či nasávací systém a výfukové
koncové kusy nie sú upchaté;
- skontrolovať činnosť bezpečnostného presostatu
proti absencii vzduchu;
- skontrolovať zásah regulačných prvkov;
- zaplombovať regulačné zariadenie prietoku
plynu (ak by sa nastavenie mali zmeniť);
- skontrolovať ohrev úžitkovej vody;
- skontrolovať tesnosť vodovodných okruhov;
- skontrolovať ventiláciu a/lebo vetranie v mie-
stnosti, kde je kotol inštalovaný tam, kde je to
potreba.
Ak by výsledok len jednej kontroly súvisiacej s
bezpečnosťou bol negatívny, nesmie byť zariadenie
uvedené do prevádzky.
163
BG
3
пЪРВОНАчАЛНА пРОВЕРКА
ТОпЛОГЕНЕРАТОР. – ЗА ТЕхНИКА.
За пускане в употреба на топлогенератора трябва::
- да се провери има ли декларация за съответствие
на инсталацията;
- да се провери съответства ли използвания газ на
този, за който е предназначен топлогенератора;
- да се провери свързването към мрежа 230V-50Hz,
спазването на поляритета L-N и заземяването;
- да се провери дали отоплителната инсталация
е пълна с вода, проверявайки дали стрелката на
манометъра на топлогенератора показва налягане
от 1-1.2 bar;
- да се провери дали крачето на обезвъздушителния
клапан е отворено и дали инсталацията е напълно
обезвъздушена;
- да се запали топлогенератора и да се провери
правилното запалване;
- да се провери дали максималното, средното и
минималното подаване на газ и съответните
налягания са съгласно посочените в книжката
(Парагр. 3.17).
- да се провери задействането на защитното
приспособление в случай, че липсва газ и
съответното време за намеса;
- да се провери намесата на главния прекъсвач,
поставен отгоре на топлогенератора;
- да се провери дали терминалите за засмукване и/
или отвеждане не са запушени;
- да се провери намесата на защитния манометър
срещу липса на въздух;
- да се провери задействането на органите за
регулиране;
- да се пломбират приспособленията за
регулиране подаването на газ (при промяна на
регулировките);
- да се провери производстваото на санитарна
топла вода;
- да се провери уплътнението на водните
инсталации;
- да се провери вентилацията и/или овъздушаването
на помещението, където следва да се извърши
инсталирането.
Ако дори една от съответните проверки за защита
се окаже негативна , инсталацията не трябва да се
пуска в употреба.