Signal targets for STW1 Standard telegram 3 (p0922 = 3)
Signal
Meaning
= ON (pulses can be enabled)
STW1.0
0 = OFF1 (braking with ramp-function generator, then pulse cancellation, ready for switching on)
1 = No OFF2 (enable is possible)
STW1.1
0 = OFF2 (immediate pulse cancellation and power-on inhibit)
1 = No OFF3 (enable possible)
STW1.2
0 = OFF3 (braking with the OFF3 ramp p1135, then pulse cancellation and power-on inhibit)
1 = Enable operation (pulses can be enabled)
STW1.3
0 = Inhibit operation (cancel pulses)
1 = Operating condition (the ramp-function generator can be enabled)
STW1.4
0 = Inhibit ramp-function generator (set the ramp-function generator output to zero)
1 = Enable the ramp-function generator
STW1.5
0 = Stop the ramp-function generator (freeze the ramp-function generator output)
1 = Enable setpoint
STW1.6
0 = Inhibit setpoint (set the ramp-function generator input to zero)
STW1.7
= Acknowledge faults
STW1.8
Reserved
STW1.9
Reserved
STW1.10
1 = Control by PLC
STW1.11
Reserved
STW1.12
Reserved
STW1.13
1 = Enable zero marks
STW1.14
Reserved
STW1.15
Reserved
<1> The drive object is ready for transfer.
<2> Without function on the TM41. The zero mark can only be switched via p4401.
1
2
DO: TM41
Terminal Module 41 (TM41) - STW1 control word interconnection (p0922 = 3)
<1>
<2>
3
4
Interconnection
[Function diagram]
[Function diagram]
parameters
internal control word
signal target
p0840 = r2090.0
[9678.3]
p0844 = r2090.1
[9678.3]
p0848 = r2090.2
[9678.3]
p0852 = r2090.3
[9678.3]
p1140 = r2090.4
[9678.3]
p1141 = r2090.5
[9678.3]
p1142 = r2090.6
[9678.3]
p2103[0] = r2090.7
[2546.1]
-
-
-
-
p0854[0] = r2090.10
[9678.3]
-
-
-
-
p1035 = p2090.13
[9678.3]
-
-
-
-
5
6
fp_9677_51_eng.vsd
16.06.10 V05.02.03
2000.00 µs
Inverted
[9682]
-
[9682]
-
[9682]
-
[9682]
-
[9682]
-
[9682]
-
[9682]
-
[8060]
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7
8
Function diagram
- 9677 -
SINAMICS