Changeover; Metering Mode - Ecolab EcoAdd Serie Instrucciones De Servicio

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 750
9.6

Changeover

9.6.1

Metering mode

Selecting a corresponding [Metering mode] ( / / / ) makes it possible to extend the
suction duration per stroke (suction stroke duration) and thus adjust the metering to high
product viscosities or challenging suction conditions.
This extension of the suction stroke duration simultaneously results in a reduction in the
max. metering output (see tables below).
Metering mode
Display
Metering output
100 %
(V)
Max. stroke frequency
at 100%
(¦)
Stroke volume
(V
)
h
Suction stroke
duration
(S
)
t
Min. metering stroke
duration
(P
)
t
The stroke frequency varies depending on the mode and calibration.
– Switching between the dosage modes means that the diaphragm metering
pump must be re-calibrated!
The calibration symbol C! is displayed on the display of the operating level.
– Once the automatic [Calibration] has been correctly carried out, the symbol
C! is hidden in the operating level again!
– The table values displayed for the max. stroke frequency (max. metering
capacity) are dependent on the pump size and calibration.
– The details about the suction stroke and metering stroke times are
theoretical values. They may vary according to calibration tolerances,
suction line lengths, back-pressure, etc.
Default
00510x
5 l/h
01110S
11,0 l/h
03003S
30 l/h
05010M
54 l/h
12003M
120 l/h
00510x
155 / min
01110S
176 / min
03003S
155 / min
05010M
159 / min
12003M
148 / min
00510x
01110S
03003S
05010M
12003M
00510x
190 ms
01110S
170 ms
03003S
190 ms
05010M
185 ms
12003M
200 ms
00510x
01110S
03003S
05010M
12003M
137
Medium
Low
4,17 l/h
3,33 l/h
9,66 l/h
7,73 l/h
25 l/h
20 l/h
45 l/h
36 l/h
100 l/h
80 l/h
141 / min
111 / min
160 / min
126 / min
141 / min
111 / min
145 / min
114 / min
135 / min
106 / min
0,53 l/h
1,1 l/h
3.4 ml
5.8 ml
13.5 ml
228 ms
342 ms
204 ms
306 ms
228 ms
342 ms
222 ms
333 ms
240 ms
360 ms
197 ms
171 ms
197 ms
192 ms
205 ms
417102276 Rev. 3-01.2019
Operation
Variable
2.5 - 5 l/h
5.8 - 11.0 l/h
15 - 30 l/h
27 - 54 l/h
60 - 120 l/h
104 - 155 / min
117 - 176 / min
104 - 155 / min
107 - 159 / min
99 - 148 / min
380 - 190 ms
340 - 170 ms
380 - 190 ms
370 - 185 ms
400 - 200 ms
Tabla de contenido
loading

Tabla de contenido