6.3.3. "Automatic mode"

Description
The system enters automatic mode either
automatically after the run-in period ends or via
a manual menu selection.
In the case of manual menu selection, the
user can choose the processing step in which
the sequence should commence.
In automatic mode, the grey water is fed
through the three tanks B1, B2 and B3 in batch
operation.
The tanks B1 and B2 are aerated.
In tank B3, the water is sterilised by a UV
lamp.
The sediments in the tanks B2 and B3 are
drained off at certain cleaning intervals.
If the power fails during automatic mode, the
system changes to automatic mode when the
power is restored and starts a new batch.
If the duration of the failure exceeds a
definable period, the system changes to run-in
mode instead of to automatic mode, and
remains there until the duration of the run-in
period has elapsed.
Setting
Select mode of operation (see chapter 6.3)
Select
Acknowledge
EN 24
Operating Manual AquaCycle 2500
Select
Acknowledge
Return to main page
In automatic mode, it is necessary to select the
operating period for starting:
-
Grey water treatment
-
Sedimentation
-
Pumping the water from tank B2 to
tank B3
-
Pumping the water from tank B1 to
tank B2
In the event of a restart, it is recommended to
always begin with a new "treatment" of the
grey water.