Start-up
FECA-01 configuration parameters – group A
CHANGED:
(group 1)
Note: The actual parameter group number depends on the drive type. Group A (group 1)
corresponds to:
•
parameter group 51 in ACS355, ACSM1, ACS580 and ACS850.
•
parameter group is typically 51/54 (group 151/154 in some variants) in ACS880 if the
adapter is installed as fieldbus adapter A/B.
For more information, refer the appropriate drive manuals.
No.
Name/Value
01
FBA TYPE
02
PROFILE
ACS355:
FB PAR 2
ACSM1:
FBA PAR2
ACS850:
FBA par2
ACS880/ACS580:
Profile
0 = CiA 402
1 = ABB Drives
profile
3 = Transparent
03
STATION ALIAS
ACS355:
FB PAR 3
ACSM1:
FBA PAR3
ACS850:
FBA par3
ACS880/ ACS580:
Station alias
04
Reserved
...
20
Description
Read-only. Shows the fieldbus adapter type.
The value cannot be adjusted by the user.
If the value is not 135, the adapter module
sets the fieldbus configuration parameters to
their default values.
Selects the communication profile used by
the adapter module. It is not recommended to
switch communication profiles during
operation.
For more information on the communication
profiles, see chapter
CANopen device profile CiA 402 selected
ABB Drives profile selected
Transparent profile selected
Configured Station Alias address used for
node addressing. Use of this alias is
activated by the master.
These parameters are not used by the
adapter module.
Communication
profiles.
Update notice
Default
135 =
EtherCAT
0 =
CiA 402
0
N/A