Interruptor automático de bastidor
Catalogue Code structure
G T G 00 K3 X 1 S F
1
2
1
1) A product belonging to the GE ACB breaker line
2
2) Product Type
L
Standard Mpact Electronic trip unit to IEC standards
H
Advanced Mpact Electronic trip unit to IEC standards 24-48V AC
Q
Advanced Mpact Electronic trip unit to IEC standards 120-240V AC
T
EntelliGuard Electronic Trip Unit to IEC Standards
3
3) Dimension of the associated breaker
G
Univeral fits into all EntelliGuard products
1
Fits into Mpact frame 1
2
Fits into Mpact frame 1
4
4) + 5) Breaker Current Rating
00
Suitable for all current ratings (EntelliGuard IEC)
04
400A
07
630A
08
800A
10
1000A
13
1250A
16
1600A
20
2000A
25
2500A
32
3200A
40
4000A
6
6) & 7) Protection & Breaker type
K1
EntelliGuard IEC. Type with LT protection,
22 LTBD bands, ST protection & STDB bands with 3 I²t bands.
K2
EntelliGuard IEC. Type with LT protection,
22 LTBD bands, ST protection,
STDB bands with 3 I²t bands & GFsum protection.
K3
EntelliGuard IEC. Type with LT protection,
22 LTBD bands, ST protection, STDB bands with 3 I²t bands,
I instantaneous protection with OFF position and GFsum protection.
K4
EntelliGuard IEC. Type with LT protection,
22 LTBD bands, ST protection, STDB bands with 3 I²t bands,
HI instantaneous protection with OFF position and GFsum protection
K9
EntelliGuard IEC. Type with LT protection,
22 LTBD bands, ST protection, STDB bands with 3 I²t bands
and I instantaneous protection with OFF position.
KA
EntelliGuard IEC. Type without protection. (Dummy)
N1
EntelliGuard IEC. Type with LT protection, 44 LTBD bands,
ST protection & STDB bands with 3 I²t bands.
N2
EntelliGuard IEC. Type with LT protection, 44 LTBD bands,
ST protection, STDB bands with 3 I²t bands & GFsum protection.
N3
EntelliGuard IEC. Type with LT protection, 44 LTBD bands,
ST protection, STDB bands with 3 I²t bands,
I instantaneous protection with OFF position and GFsum protection.
N4
EntelliGuard IEC. Type with LT protection, 44 LTBD bands,
ST protection, STDB bands with 3 I²t bands,
HI instantaneous protection with OFF position and GFsum protection.
N5
EntelliGuard IEC. Type with LT protection, 44 LTBD bands,
ST protection, STDB bands with 3 I²t bands,
I instantaneous protection , GFsum and/or GFct protection.
All protection devices with OFF position.
N6
EntelliGuard IEC. Type with LT protection, 44 LTBD bands,
ST protection, STDB bands with 3 I²t bands,
I instantaneous protection , GFsum and/or GFct Alarm Function.
All protection devices & Alarms with OFF position.
N7
EntelliGuard IEC. Type with LT protection, 44 LTBD bands,
ST protection, STDB bands with 3 I²t bands,
HI instantaneous protection , GFsum and/or GFct protection.
All protection devices with OFF position.
3
4
5
(Sensor rating)
6
7
8
N8
EntelliGuard IEC. Type with LT protection, 44 LTBD bands,
ST protection, STDB bands with 3 I²t bands,
HI instantaneous protection , GFsum and/or GFct Alarm Function.
All protection devices & Alarms with OFF position.
N9
EntelliGuard IEC. Type with LT protection, 44 LTBD bands,
ST protection, STDB bands with 3 I²t bands and
I instantaneous protection
All protection devices with OFF position.
M3
Mpact. Type with LT protection, 22 LTBD bands, ST protection,
STDB bands with 3 I²t bands and
I instantaneous protection with OFF position.
M4
Mpact. Type with LT protection, 22LTBD bands, ST protection,
STDB bands with 3 I²t bands, I instantaneous protection, GFsum
and/or GFct protection. All protection devices with OFF position.
M5
Mpact. Type with LT protection, 22 LTBD bands, ST protection,
STDB bands with 3 I²t bands, I instantaneous protection with
OFF position and GFsum protection.
MA Mpact. Type without protection. (Dummy)
8
8) Zone selective Interlocking Features
Z
Zone Selective Interlock operational on ST and GF functions,
user selectable.
T
Zone Selective Interlock operational on ST, I or HI and GF functions,
user selectable.
X
Non Functional.
9
9) Advanced Features & Communication
1
RELT Function present
2
Modbus Communication & RELT function present
3
Profibus Communication & RELT function present
4
Full Measurement package & RELT function present
5
Full Measurement package, Protective relaying,
Input/ Outputs & RELT function present
6
Full Measurement package, Input/ Outputs, waveform capture,
Modbus communication & RELT function present
7
Full Measurement package, , Input/ Outputs, waveform capture,
Profibus communication & RELT function present
8
Full Measurement package, Protective relaying, Input/ Outputs,
waveform capture, Modbus communication & RELT function present
9
Full Measurement package, Protective relaying, Input/ Outputs,
waveform capture, Profibus communication & RELT function present
X
None of these functions present
10
10) Trip Unit Reset options
M
After trip LOCAL reset is required
A
After Trip Breaker is reset automatically
S
Selector switch Manual/ automatic reset
X
Not selected
11
11) Trip Unit Mode of Supply
F
Fitted to Breaker in Factory
R
Field mountable device
12
12) ...15) Reserved for future use
TRIP UNIT
EntelliGuard G
9
10
11
2
.9
12
15
2-59