Pixsys ATR244-12ABC Manual De Instalación página 69

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

312 r.2.s.e.
Retransmission 2 State Error
Determines retransmission 2 value in case of error or anomaly.
If the retransmission output is 0-10V:
0 V. Default
0 V
10 V.
10 v
If the retransmission output is 0-20 mA or 4-20 mA:
0 mA. Default
0 ma
4 mA.
4 ma
20 mA.
20 ma
21.5 mA.
21.5ma
313÷317
Reserved Parameters - Group U
Reserved parameters - Group U
GROUP V -
ser.
318 sL.ad.
Slave Address
Selects slave address for serial communication.
1...254. Default: 247.
319 bd.rt.
Baud Rate
Selects baudrate for serial communication
1200 bit/s
1.2 k
2400 bit/s
2. 4 k
4800 bit/s
4.8 k
9600 bit/s
9.6 k
19200 bit/s (Default)
19.2 k
28800 bit/s
28.8 k
38400 bit/s
38. 4 k
57600 bit/s
57.6 k
115200 bit/s
115.2k
320 s.p.p.
Serial Port Parameters
Selects the format for the modbus RTU serial communication.
8 bit, no parity, 1 stop bit (Default)
8-N-1
8 bit, even parity, 1 stop bit
8-E-1
8 bit, odd parity, 1 stop bit
8-o-1
8 bit, no parity, 2 stop bit
8-N-2
8 bit, even parity, 2 stop bit
8-E-2
8 bit, odd parity, 2 stop bit
8-o-2
321 se.de.
Serial Delay
Selects serial delay
0...100 ms. Default: 5 ms.
322 off.L.
Off Line
Selects the off-line tine. If there is no serial communication during the selected time, the
controller switches-off the command output.
Offline disabled (Default)
0
tenths of second.
0.1-600.0
323÷327
Reserved Parameters - Group V
Reserved parameters - Group V
- Serial
(not available on ATR244-12ABC)
User manual - ATR244 - 69

Hide quick links:

Tabla de contenido
loading

Este manual también es adecuado para:

Atr244-12abc-tAtr244-13abcAtr244-23a-tAtr244-23bc-t

Tabla de contenido