Command Hysteresis - Pixsys ATR244-12ABC Manual De Instalación

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

37
Reserved
rEs.
Reserved parameter.
38
Action type 1
Ac.t. 1
Action type to control process 1.
Heating (N.A.) (Default)
HEAt
Cooling (N.C.)
cooL
39

Command Hysteresis 1

c.HY. 1
Hysteresis to control process 1 in ON/OFF.
-9999..+9999 [digit
40
Lower Limit Setpoint 1
L.L.S. 1
Lower limit setpoint selectable for command setpoint 1.
-9999..+30000 [digit
41
Upper Limit Setpoint 1
U.L.S. 1
Upper limit setpoint selectable for command setpoint 1.
-9999..+30000 [digit
42
Command Reset 1
c.re. 1
Type of reset for command contact 1 (always automatic in P.I.D. functioning)
Automatic Reset (Default)
A. rEs.
Manual Reset (by keyboard or by digital input)
M. rEs.
Manual Reset Stored (keeps relay status also after an eventual power failure)
M.rEs.S.
Automatic reset with timed activation. The command remains active for the time set
A.rEs.t.
on the parameter 45
to act again, the conditions for activating the command must disappear.
43
Command State Error 1
c.S.e. 1
State of contact for command 1 output in case of error.
If the command output 1 (Par. 35
Contact or valve open. Default
open
Contact or valve closed.
CLose
If the command output 1 is digital output (SSR):
Digital output OFF. Default
off
Digital output ON.
on
If the command output 1 is 0-10V:
0 V. Default
0 V
10 V.
10 v
If the command output 1 is 0-20 mA or 4-20 mA:
0 mA. Default
0 ma
4 mA.
4 ma
20 mA.
20 ma
21.5 mA.
21.5ma
44
Command Led 1
c.Ld. 1
Defines led C1 state corresponding to the relevant output. If the valve command is selected, this
parameter is not managed.
ON with open contact or SSR switched off. If command AO1, ON with output 0%, OFF if
o.c.
100% and flashing between 1% and 99%.
ON with closed contact or SSR switched on. If command AO1 ON with output 100%,
c.c.
OFF if 0% and flashing between 1% and 99%. (Default)
] (degrees.tenths for temperature sensors). Default 0.2.
1 p. 74
] (degrees.tenths for temperature sensors). Default 0.
1 p. 74
] (degrees for temperature sensors). Default 1750.
1 p. 74
, even if the conditions generating it are missing. To be able
c.de.1.
c.ou. 1
) is relay or valve:
User manual - ATR244 - 39