Modbus
Description
address
1229
Cooling output percentage with regulation 2 in double loop (0-10000)
1230
Cooling output percentage with regulation 2 in double loop (0-1000)
1231
Cooling output percentage with regulation 2 in double loop (0-100)
Command output manual reset for regulation loop 1: write 0 to reset the
1232
command output.
In reading 0=reset not allowed, 1=reset allowed
Alarms manual reset: write 0 to reset all alarms.
In reading 0=reset not allowed, 1=reset allowed
1233
Bit0 = Alarm 1
Bit1 = Alarm 2
Bit2 = Alarm 3
Command output manual reset for regulation loop 2: write 0 to reset the
1234
command output.
In reading 0=reset not allowed, 1=reset allowed
1235
Alarm 1 remote stauts (0=absent, 1=present)
1236
Alarm 2 remote stauts (0=absent, 1=present)
1237
Alarm 3 remote stauts (0=absent, 1=present)
1238
Alarm 4 remote stauts (0=absent, 1=present)
1239
Alarm 5 remote stauts (0=absent, 1=present)
1240
Alarm 6 remote stauts (0=absent, 1=present)
1241
Value AO1 by serial (Par. 298
1242
Value AO2 by serial (Par. 308
1243
Tare of zero AI1 (1=tare; 2=reset tare)
1244
Tare of zero AI2 (1=tare; 2=reset tare)
Tare of zero average between AI1 and AI2 [(AI1 + AI2) /2]
1245
(1=tare; 2=reset tare)
Tare of zero difference between AI1 and AI2 (AI1 - AI2)
1246
(1=tare; 2=reset tare)
Tare of zero module of the difference between AI1 and AI2 (|AI1 - AI2|)
1247
(1=tare; 2=reset tare)
Tare of zero sum of AI1 and AI2 (AI1 + AI2)
1248
(1=tare; 2=reset tare)
1249
Value of remote setpoint by command 1 serial
1250
Value of remote setpoint by command 2 serial
1251
Alarm 1 lower setpoint if Par. 123
1252
Alarm 2 lower setpoint if Par. 141
1253
Alarm 3 lower setpoint if Par. 159
1254
Alarm 4 lower setpoint if 177
1255
Alarm 5 lower setpoint if Par. 195
1256
Alarm 6 lower setpoint if Par. 213
1300
Setpoint 1 of regulation loop 1, with decimal point selection
1301
Setpoint 2 of regulation loop 1, with decimal point selection
1302
Setpoint 3 of regulation loop 1, with decimal point selection
1303
Setpoint 4 of regulation loop 1, with decimal point selection
1304
Setpoint 1 of regulation loop 2, with decimal point selection
1305
Setpoint 2 of regulation loop 2, with decimal point selection
1306
Setpoint 3 of regulation loop 2, with decimal point selection
1307
Setpoint 4 of regulation loop 2, with decimal point selection
Alarm 1 setpoint, with decimal point selection
1308
Alarm 1 upper setpoint if Par. 123
28 - ATR244 - User manual
Bit3 = Alarm 4
Bit4 = Alarm 5
Bit5 = Alarm 6
=
rtM. 1
md.bus
=
rtM.2
md.bus
AL.1.F .
AL.2.F .
AL.3.F .
=
AL. 4.F .
A.band
AL.5.F .
AL.6.F .
AL.1.F .
)
)
=
(degrees with tenth)
A.band
=
(degrees with tenth)
A.band
=
(degrees with tenth)
A.band
(degrees with tenth)
=
(degrees with tenth)
A.band
=
(degrees with tenth)
A.band
=
A.band
Read
Reset
Write
value
RO
0
RO
0
RO
0
R/W 0
R/W 0
R/W 0
R/W 0
R/W 0
R/W 0
R/W 0
R/W 0
R/W 0
R/W 0
R/W 0
R/W 0
R/W 0
R/W 0
R/W 0
R/W 0
R/W 0
R/W 0
R/W 0
R/W EEPROM
R/W EEPROM
R/W EEPROM
R/W EEPROM
R/W EEPROM
R/W EEPROM
R/W EEPROM
R/W EEPROM
R/W EEPROM
R/W EEPROM
R/W EEPROM
R/W EEPROM
R/W EEPROM
R/W EEPROM
R/W EEPROM