GROUP S -
ct
287 ct F.
Current Transformer Function
Enables the C.T. input and selects the net frequency
Disabled (Default)
DiSab.
50 Hz
50 Hz
60 Hz
60 Hz
288 ct v.
Current Transformer Value
Selects the amperometric transformer full-scale
Ampere (Default: 50)
1..200
289 H.b.a.r.
Heater Break Alarm Reference Command
Defines the reference command for the heater break alarm and the overcurrent alarm.
Command 1 (Default)
cmd. 1
Command 2
cmd. 2
290 H.b.a.t.
Heater Break Alarm Threshold
Heater Break Alarm activation threshold
Alarm disabled. (Default:)
0
Ampere.
0.1-200.0
291 ocu.t.
Overcurrent Alarm Threshold
Overcurrent alarm threshold.
Alarm disabled. (Default)
0
Ampere
0.1-200.0
292 H.b.a.d.
Heater Break Alarm Delay
Heater Break Alarm and overcurrent alarm activation delay.
00:00-60:00
293÷297
Reserved Parameters - Group S
Reserved parameters - Group S
GROUP T -
a.o. 1
298 rtM. 1
Retransmission 1
Retransmission for output. Parameters 300 and 301 define lower and upper limit of the operating
scale.
Disabled (Default)
diSab.
Command 1 setpoint
c.1.SPv
Alarm 1 setpoint
AL. 1
Alarm 2 setpoint
AL. 2
Retransmits the value written on word 1241
Md.bus
Value read on input AI1
A.iN.1
Value read on input AI2
A.in.2
Arithmetic average of the value read on inputs AI1 and AI2 [(AI1+AI2)/2]
MEAn
Difference of the values read on inputs AI1 and AI2 (AI1-AI2)
diFF .
Module of the difference of the values read on inputs AI1 and AI2 (|AI1-AI2|)
Ab.dif .
Sum of values read on inputs AI1 and AI2 (AI1+AI2)
SuM
Command 2 setpoint
c.2.SPv
Ampere from current transformer
AMPer.
299 r. 1 .ty.
Retransmission 1 Type
Selects the retransmission type for AO1
Output 0...10 V.
0.10 v
Output 4...20 mA. Default
4.20ma
- Current transformer
mm:ss (Default: 01:00)
- Retransmission 1
(only on ATR244-13ABC and 23xx-T)
User manual - ATR244 - 67