300 r. 1 . L.L.
Retransmission 1 Lower Limit
Retransmission 1 lower limit range (value related to 10 V or 0/4 mA).
-9999..+30000 [digit
301 r. 1 . u.L.
Retransmission 1 Upper Limit
Retransmission 1 upper limit range 2 (value related to 10 V or 20 mA).
-9999..+30000 [digit
302 r. 1 .s.e.
Retransmission 1 State Error
Determines retransmission 1 value in case of error or anomaly
If the retransmission output is 0-10V:
0 V. Default
0 V
10 V.
10 v
If the retransmission output is 0-20 mA or 4-20 mA:
0 mA. Default
0 ma
4 mA.
4 ma
20 mA.
20 ma
21.5 mA.
21.5ma
303÷307
Reserved Parameters - Group T
Reserved parameters - Group T
GROUP U -
a.o. 2
308 rtM.2
Retransmission 2
Retransmission for output AO2. Parameters 310 and 311 define lower and upper limit of the
operating scale.
Disabled (Default)
diSab.
Command 1 setpoint
c.1.SPv
Alarm 1 setpoint
AL. 1
Alarm 2 setpoint
AL. 2
Retransmits the value written on word 1242
Md.bus
Value read on input AI1
A.iN.1
Value read on input AI2
A.in.2
Arithmetic average of the value read on inputs AI1 and AI2 [(AI1+AI2)/2]
MEAn
Difference of the values read on inputs AI1 and AI2 (AI1-AI2)
diFF .
Module of the difference of the values read on inputs AI1 and AI2 (|AI1-AI2|)
Ab.dif .
Sum of values read on inputs AI1 and AI2 (AI1+AI2)
SuM
Command 2 setpoint
c.2.SPv
Ampere from current transformer
AMPer.
309 r.2.ty.
Retransmission 2 Type
Selects the retransmission type for AO2
Output 0...10 V.
0.10 v
Output 4...20 mA. Default
4.20ma
310 r.2. L.L.
Retransmission 2 Lower Limit
Retransmission 2 lower limit range (value related to 10 V or 0/4 mA).
-9999..+30000 [digit
311 r.2. u.L.
Retransmission 2 Upper Limit
Retransmission 2 upper limit range 2 (value related to 10 V or 20 mA).
-9999..+30000 [digit
68 - ATR244 - User manual
] (degrees if temperature), Default: 0.
1 p. 74
] (degrees if temperature), Default: 1000.
1 p. 74
- Retransmission 2
] (degrees if temperature), Default: 0.
1 p. 74
] (degrees if temperature), Default: 1000.
1 p. 74
(only on ATR244-23XX-T)