150 A.2.S.e.
Alarm 2 State Error
Alarm 2 output status in case of error
If the alarm output is relay
Contact or open valve. Default
open
If the alarm output is digital (SSR):
Digital output OFF. Default
off
151 A.2.Ld.
Alarm 2 Led
Defines the status of the led
ON with open contact or DO switched off.
o.c.
ON with closed contact or DO switched on. (Default)
c.c.
152 a.2.de.
Alarm 2 Delay
Alarm 2 Delay. -60:00..60:00 mm:ss (hh:mm if
Negative value: delay when exit alarm status.
Positive value: delay when enter alarm status
153 A.2.S.p.
Alarm 2 Setpoint Protection
Allows or not to change the alarm 2 setpoint
Editable by the user (Default)
FrEE
Protected
Lock
Protected and not visualized
HidE
154 A.2.Lb.
Alarm 2 Label
Selects the message displayed in case of alarm 2 intervention.
Disabled. (Default) 0.
disab.
Message 1 (see table on paragraph 14.1)
lb. 01
..
Message 20 (see table on paragraph 14.1)
lb. 20
Custom message (modifiable by the user through the App or via modbus)
user.l.
155÷158
Reserved Parameters - Group H
Reserved parameters - Group H
GROUP I -
AL. 3
159 AL.3.f.
Alarm 3 Function
Alarm 3 selection.
Disabled (Default)
diSab.
Absolute Upper Activation. Absolute referred to the process, active over
Ab.up .A.
Absolute Lower Activation. Absolute referred to the process, active under
Ab.Lo.a.
Band alarm (command setpoint ± alarm setpoint)
bAnd
Upper Deviation alarm
up .dev .
Lower Deviation alarm
Lo.dev .
Absolute Command Upper Activation. Absolute alarm referred to the command
Ab.c.u.A.
setpoint, active over
Absolute Command Lower Activation. Absolute alarm referred to the command
Ab.c.L.A.
setpoint, active under
Status alarm (active in RUN/START)
run
Cold actuator auxiliary (Cold action in double loop)
cooL
Probe error. Alarm active in case of sensor rupture.
Prb.er.
Related to timer 1
tMr.1
Related to timer 2
tMr.2
Related to both timers
tMr.1.2
Remote. The alarm is enabled by the word 1237
rEM.
Digital Input 1. Active when digital input 1 is active.
d.i. 1
Digital Input 2. Active when digital input 2 is active.
d.i. 2
Digital Input 3. Active when digital input 3 is active.
d.i. 3
A2
in correspondence of the relevant output.
- Alarm 3
Contact or closed valve.
CLose
Digital output ON.
on
=
). Default: 00:00.
AL.2.F .
c. aux
User manual - ATR244 - 51