GROUP C -
cmd. 1
35
Command Output 1
c.ou. 1
Selects the command output related to the process1 and the outputs related to the alarms.
Command on relay output Q2.
c. o2
Command on relay output Q1. (Default)
c. o1
Command on digital output
c. SSr
Servo-valve command with open loop on Q1 and Q2 relays
c. vAL.
Command 0-10 V on analogue output AO1.
c.0-10
Command 4-20 mA on analogue output AO1.
c. 4-20
Command 0-10 V on analogue output AO1 with split-range function: the analogue
0.10.S.R.
output sets the cooling action from 0 to 5V and heating action from 5 to 10V.
Command 4-20 mA on analogue output AO1 with split-range function: the analogue
4.20.S.R.
output sets the cooling action from 4 to 12mA and heating action from 12 to 20mA.
Servo-valve command with open loop on Q2 and Q3 relays (not avaiable for -12xxx)
c.VAL.c.
ATR244-12ABC and ATR244-12ABC-T
Command
Q2
c. o2
Q1
c. o1
DO1
c. SSr
Q1(open) Q2(close)
c. vAL.
(
)
AO1 (0..10 V)
c.0-10
0.10.S.R.
(
)
AO1 (4..20 mA)
c. 4-20
4.20.S.R.
ATR244-13ABC
Command
Q2
c. o2
Q1
c. o1
DO1
c. SSr
Q1(open) Q2(close)
c. vAL.
(
)
AO1 (0..10 V)
c.0-10
0.10.S.R.
(
)
AO1 (4..20 mA)
c. 4-20
4.20.S.R.
Q2(open) Q3(close)
c. vAL.c.
ATR244-23A-T and ATR244-23BC-T
Command
Q2
c. o2
Q1
c. o1
DO1
c. SSr
Q1(open) Q2(close)
c. vAL.
(
)
AO1 (0..10 V)
c.0-10
0.10.S.R.
(
)
AO1 (4..20 mA)
c. 4-20
4.20.S.R.
Q2(open) Q3(close)
c. vAL.c.
NB: if an output is used for functions other than alarms (for example retransmission or command n°
2), this resource will no longer be available as an alarm and the related group will be hidden from the
parameter list. The correspondence of the functions/outputs remains however that indicated in the
tables above.
36
Command Process 1 (only on ATR244-23XX-T)
c.Pr. 1
Selects process value related to process 1 and to command output 1.
Value read on input AI1. (Default)
A.in.1
Value read on input AI2.
A.in.2
Arithmetic average of the value read on inputs AI1 and AI2 [(AI1-AI2)/2].
MEAn
Difference of the values read on inputs AI1 and AI2 (AI1-AI2).
diFF .
Module of the difference of the values read on inputs AI1 and AI2 (|AI1-AI2|).
Ab.dif .
Sum of values read on inputs AI1 and AI2 (AI1+AI2).
SuM
38 - ATR244 - User manual
- Outputs and regulation Process 1
AL. 1
Q1
Q2
Q1
DO1
Q1
Q1
AL. 1
Q1
Q2
Q1
Q3
Q1
Q1
Q1
AL. 1
Q1
Q2
Q1
Q3
Q1
Q1
Q1
AL. 2
DO1
DO1
Q2
DO2
Q2
Q2
AL. 2
AL. 3
Q3
DO1
Q3
DO1
Q2
Q3
DO1
DO2
Q2
Q3
Q2
Q3
DO1
DO2
AL. 2
AL. 3
Q3
DO1
Q3
DO1
Q2
Q3
DO1
DO2
Q2
Q3
Q2
Q3
DO1
DO2
AL. 3
AL. 4
DO2
AO1
DO2
AO1
DO2
AO1
AO1
-
DO1
DO2
DO1
DO2
AL. 4
AL. 5
DO2
AO1
DO2
AO1
DO2
AO1
AO1
-
DO1
DO2
DO1
DO2
AO1
-
AL. 4
AL. 5
DO2
AO1
DO2
AO1
DO2
AO1
AO1
AO2
DO1
DO2
DO1
DO2
AO1
AO2
AL. 6
AO2
AO2
AO2
-
AO2
AO2
-