185 a. 4 .re.
Alarm 4 Reset
Alarm 4 contact reset type (always automatic if
Automatic reset (Default)
A. rEs.
Manual reset (manual reset by keyboard or by digital input)
M. rEs.
Stored manual reset (keeps the output status also after a power failure)
M.rEs.S.
Automatic reset with timed activation. The alarm remains active for the time set on the
A. rEs.t.
parameter 188
again, the alarm conditions must disappear.
186 A. 4 .S.e.
Alarm 4 State Error
Alarm 4 output status in case of error.
If the alarm output is digital (SSR):
Digital output OFF. Default
off
If the alarm output is 0-10V:
0 V. Default
0 V
If the alarm output is 0-20 mA or 4-20 mA:
0 mA. Default
0 ma
4 mA.
4 ma
187 rES.
Reserved
Reserved parameter
188 a. 4 .de.
Alarm 4 Delay
Alarm 4 Delay.
-60:00..60:00 mm:ss (hh:mm if
Negative value: delay when exit alarm status.
Positive value: delay when enter alarm status
189 A. 4 .S.p.
Alarm 4 Setpoint Protection
Allows or not to change the alarm 4 setpoint.
Editable by the user (Default)
FrEE
Protected
Lock
Protected and not visualized
HidE
190 A. 4 .Lb.
Alarm 4 Label
Selects the message displayed in case of alarm 4 intervention.
Disabled. (Default) 0.
disab.
Message 1 (see table on paragraph 14.1) ..
lb. 01
Message 20 (see table on paragraph 14.1)
lb. 20
Custom message (modifiable by the user through the App or via modbus)
user.l.
191÷194
Reserved Parameters - Group J
Reserved parameters - Group J
GROUP K -
AL. 5
195 AL.5.f.
Alarm 5 Function
Alarm 5 selection 5.
Disabled (Default)
diSab.
Absolute Upper Activation. Absolute referred to the process, active over
Ab.up .A.
Absolute Lower Activation. Absolute referred to the process, active under
Ab.Lo.a.
Band alarm (command setpoint ± alarm setpoint)
bAnd
Upper Deviation. alarm
up .dev .
Lower Deviation alarm
Lo.dev .
Absolute Command Upper Activation. Absolute alarm referred to the command
Ab.c.u.A.
setpoint, active over.
Absolute Command Lower Activation. Absolute alarm referred to the command
Ab.c.L.A.
, even if the conditions generating it are missing. To be able to act
a. 4.de.
AL. 4.F .
- Alarm 5
(only on ATR244-13ABC and ATR244-23XX-T)
=
AL. 4.F .
c. Aux
on
10 v
20 ma
21.5ma
=
). Default: 00:00.
c. aux
).
Digital output ON.
10 V.
20 mA.
21.5 mA.
User manual - ATR244 - 55