Pixsys ATR244-12ABC Manual De Instalación página 45

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

89
Max Gap Tune 1
m.G.t. 1
Selects the max. process-setpoint gap beyond which the automatic tune recalculates PID
parameters of process 1.
0-10000 [digit
1 p. 74
90
Minimum Proportional Band 1
mn.p. 1
Selects the min. proportional band 1 value selectable by the automatic tune for the P.I.D.
regulation of process 1.
0-10000 [digit
1 p. 74
91
Maximum Proportional Band 1
ma.p. 1
Selects the max. proportional band 1 value selectable by the automatic tune for the P.I.D.
regulation of process 1.
0-10000 [digit
1 p. 74
92
Minimum Integral Time 1
mn. i . 1
Selects the min. integral time 1 value selectable by the automatic tune for the P.I.D. regulation of
process 1.
0.0...1000.0 seconds. Default: 30.0 s.
93
Overshoot Control Level 1
o.c.L. 1
The overshoot control function prevents this event during device switching on or when the
setpoint is modified.
Setting a too low value the overshoot may not be fully absorbed, while with high values the
process could reach the setpoint more slowly.
Disab.
Lev. 1
Lev. 2
94÷97
Reserved Parameters - Group E
Reserved parameters - Group E
GROUP F -
reG.2
98
Tune 2
tun.2
Selects autotuning type for command 2
Disabled. If proportional band and integral time paramters are to selected to zero, the
diSab.
regulation is ON/OFF type. (Default)
Automatic (Automatic P.I.D. parameters calculation )
Auto
Manual (launch by keyboards or by digital input)
Manu.
Once (P.I.D. parameters calculation only at first start)
OncE
Synchronized (Autotuning managed by serial)
SYncH.
99
Setpoint Deviation Tune 2
s.d.t.2
Selects deviation from command setpoint 2 as threshold used by
autotuning to calculate P.I.D. parameters.
0-10000 [digit
1 p. 74
100 p.b. 2
Proportional Band 2
Proportional band or process 2 P.I.D. regulation (Process inertia).
0 ON / OFF if t.i. equal to 0 (Default)
1...10000 [digit
1 p. 74
101 i.t. 2
Integral Time 2
Integral time for process 2 P.I.D. regulation (process intertia duration).
0.0...2000.0 seconds (0.0 = integral disabled), Default 0.0
] (degrees.tenths for temp. sensors). Default: 2.0
] (degrees.tenths for temp. sensors). Default: 3.0
] (degrees.tenths for temp. sensors). Default: 80.0
Lev. 3
Lev. 4
Lev. 5 (Default)
- Autotuning and PID 2
] (degrees.tenths for temp. sensors). Default: 30.0.
] (degrees.tenths for temp. sensors).
Lev. 6
Lev. 7
Lev. 8
(only on ATR244-23XX-T)
Lev. 9
Lev. 10
User manual - ATR244 - 45

Hide quick links:

Tabla de contenido
loading

Este manual también es adecuado para:

Atr244-12abc-tAtr244-13abcAtr244-23a-tAtr244-23bc-t