45
Command Delay 1
c.de. 1
Command 1 delay (only in ON / OFF functioning).
-60:00..60:00 mm:ss. Default: 00:00.
Negative: delay when turning off output.
Positive: delay when turning on output.
46
Command Setpoint Protection 1
c.S.p. 1
Allows or not to modify command setpoint 1 value
Modification allowed (Default)
FrEE
Protected
Lock
Free Initialized. At start, setpoint 1 of command 1 is initialized to the value set on
FR.iN.
parameter 51
47
Valve Time 1
vA.t. 1
Valve time related to command 1 (declared by the manufacturer of the valve)
1...300 seconds. Default: 60.
48
Automatic / Manual 1
a.ma. 1
Enables the automatic/manual selection for command 1
Disabled (Default)
diSab.
Enabled
Enab.
Enabled with memory
En.Sto.
49
Initial State
ini.S.
Choose the state of the controller when turning it on. This only works on the RS485 version or by
enabling the Start/Stop from digital input or
Start (Default)
Start
Stop
stop
Stored. State of Start/Stop prior to switching off.
Store.
50
State Valve Saturation
S.vA.S.
Select the valve status when the output percentage is 100%
The valve opening relay is activated for a time equal to 5% of the valve time
PERc.
The valve opening relay is always active
FiXEd
51
Initial Value Setpoint 1
i.SP. 1
Determines the initial value (at start) of setpoint 1 of command 1 when
parameter 46
c.S.p .1
-9999..+30000 [digit
52÷53
Reserved Parameters - Group C
Reserved parameters - Group C
40 - ATR244 - User manual
(Initial Value Setpoint 1).
i.SP .1
(Command Setpoint Protection 1)
] (degrees for temperature sensors). Default 0.
1 p. 74
SET
button.
is selected on
FR.iN.