Analogue Input AI2 (only ATR244-23x)
5.1.c
Shield/Schermo
18
AI2
TC
17
Shield/Schermo
Rosso
18
Red
Bianco
17
AI2
White
Rosso
16
Red
Shield/Schermo
16
AI2
17
15
+V
17
AI2 V mA
18
Shield/Schermo
CT input (only on ATR244-13ABC and 23xx-T)
5.1.d
13ABC
23x
11
22
13
23
Digital inputs
5.1.e
12/13 ABC 12ABC-T 23x
DI/O1
(PNP)
DI2
13
DI/O2
13
DI/O2
(PNP)
(PNP)
(PNP)
DI1
14
DI/O1
DI3
14
(PNP)
(PNP)
(PNP)
DI4
15
15
0V
0V
(PNP)
16
16
+V
0V
+V
+V
Serial inputs (only ATR244-xxxxx-T)
5.1.f
ATR244-12ABC-T
Shield/Schermo
(B)
11
RS485
12
(A)
ATR244-23x
Shield/Schermo
(B)
19
RS485
9
(A)
14 - ATR244 - User manual
For thermocouples K, S, R, J, T, E, N, B.
• Comply with polarity
• For possible extensions, use compensated cable and terminals suitable for
the thermocouples used (compensated).
• When shielded cable is used, it should be grounded at one side only.
For thermoresistances PT100, Ni100.
• For the three-wire connection use wires with the same section.
• For the two-wire connection short-circuit terminals 16 and 18.
• When shielded cable is used, it should be grounded at one side only.
RED/ROSSO
WHITE/BIANCO
RED/ROSSO
For thermoresistances NTC, PTC, PT500, PT1000 and linear potentiometers.
When shielded cable is used, it should be grounded at one side only to avoid
ground loop currents.
For linear signals in Volt and mA
• Comply with polarity
• When shielded cable is used, it should be grounded at one side only to
avoid ground loop currents.
• To power the sensor connected to AI2 through +V (terminal 15 or 25),
short-circuit 0 V (terminal 14 or 24) with AI2 ground input (terminal 17).
• + V at 12Vdc or 24Vdc can be selected by configuring parameter 282
(GROUP R -
- Display and interface).
diSP.
To enable CT input, modify parameter 287
• Input for 50 mA amperometric transformer.
• Sampling time 100 ms.
• Configurable by parameters.
Digital inputs can be enabled by parameters.
20
21
Close pin "DIx" on pin "+V" to enable digital input.
22
23
It is possible to put in parallel the digital inputs of different devices joining
24
together the 0V pins (15).
25
Modbus RS485 communication.
RTU Slave with galvanic insulation.
It is recommended to use the twisted and shielded cable for communi-
cations.
.
ct F