60
Upper Limit Setpoint 2
U.L.S.2
Upper limit setpoint selectable for command setpoint 2.
-9999..+30000 [digit
61
Command Reset 2
c.re.2
Type of reset for command contact 2 (always automatic in P.I.D. functioning)
Automatic Reset (Default)
A. rEs.
Manual Reset (by keyboard or by digital input)
M. rEs.
Manual Reset Stored (keeps relay status also after an eventual power failure)
M.rEs.S.
Automatic reset with timed activation. The command remains active for the time set
A.rEs.t.
on the parameter 64 c.de.2., even if the conditions generating it are missing. To be able
to act again, the conditions for activating the command must disappear.
62
Command State Error 2
c.S.e.2
State of contact for command 2output in case of error.
If the command output 2 (Par. 54
Contact or valve open. Default
open
Contact or valve closed.
CLose
If the command output 2 is digital output (SSR):
Digital output OFF. Default
off
Digital output ON.
on
If the command output 2 is 0-10V:
0 V. Default
0 V
10 V.
10 v
If the command output 2 is 0-20 mA or 4-20 mA:
0 mA. Default
0 ma
4 mA.
4 ma
20 mA.
20 ma
21.5 mA.
21.5ma
63
Command Led 2
c.Ld.2
Defines led
C2
parameter is not managed.
ON with open contact or SSR switched off. If command AO2, ON with output 0%, OFF if
o.c.
100% and flashing between 1% and 99%.
ON with closed contact or SSR switched on. If command AO2 ON with output 100%,
c.c.
OFF if 0% and flashing between 1% and 99%. (Default)
64
Command Delay 2
c.de.2
Command 2 delay (only in ON / OFF functioning).
-60:00..60:00 mm:ss. Default: 00:00.
Negative: delay when turning off output.
Positive: delay when turning on output.
65
Command Setpoint Protection 2
c.S.p.2.
Allows or not to modify command setpoint 2 value
Modification allowed (Default)
FrEE
Protected
Lock
Free Initialized. At start, setpoint 1 of command 2 is initialized to the value set on
FR.iN.
parameter 70
66
Valve Time 2
vA.t.2
Valve time related to command 2 (declared by the manufacturer of the valve)
1...300 seconds. Default: 60.
42 - ATR244 - User manual
] (degrees for temperature sensors). Default 1750.
1 p. 74
state corresponding to the relevant output. If the valve command is selected, this
(Initial Value Setpoint 2).
i.SP .2
) is relay or valve:
c.ou.2