Modbus
Description
address
Start/Stop
1214
0=controller in STOP
1=controller in START
Hold conversion ON/OFF
1215
0=Hold conversion OFF
1=Hold conversion ON
Tune management for regulation loop 1
With automatic Tune (par. 73
0=autotunig function OFF
1=autotuning ON
With manual Tune (par. 73
0=autotunig function OFF
1216
1=autotuning ON
With synchronized Tune (par. 73
0=autotunig function OFF
1=command output OFF (forces the cooling)
2=command output ON (forces the heating)
3=autotuning ON
4=autotuning ended
Tune management for regulation loop 2
With automatic Tune (par. 98
0=autotunig function OFF
1=autotuning ON
With manual Tune (par. 98
0=autotunig function OFF
1217
1=autotuning ON
With synchronized Tune (par. 98
0=autotunig function OFF
1=command output OFF (forces the cooling)
2=command output ON (forces the heating)
3=autotuning ON
4=autotuning ended
Automatic/manual selection for regulation loop 1
1218
0=automatic; 1=manual
Automatic/manual selection for regulation loop 2
1219
0=automatic; 1=manual
Command output percentage for regulation loop 1 (0-10000)
1220
Heating output percentage with regulation 1 in double loop (0-10000)
Command output percentage for regulation loop 1 (0-1000)
1221
Heating output percentage with regulation 1 in double loop (0-1000)
Command output percentage for regulation loop 1 (0-100)
1222
Heating output percentage with regulation 1 in double loop (0-100)
1223
Cooling output percentage with regulation 1 in double loop (0-10000)
1224
Cooling output percentage with regulation 1 in double loop (0-1000)
1225
Cooling output percentage with regulation 1 in double loop (0-100)
Command output percentage for regulation loop 2 (0-10000)
1226
Heating output percentage with regulation 2 in double loop (0-10000)
Command output percentage for regulation loop 2 (0-1000)
1227
Heating output percentage with regulation 2 in double loop (0-1000)
Command output percentage for regulation loop 2 (0-100)
1228
Heating output percentage with regulation 2 in double loop (0-100)
=
):
tun. 1
Auto
=
or
tun. 1
manu.
OncE
=
) :
tun. 1
SYncH.
=
):
tun.2
Auto
=
or
tun.2
manu.
OncE
=
) :
tun.2
SYncH.
):
):
Read
Reset
Write
value
R/W 0
R/W 0
RO
0
R/W 0
R/W 0
RO
0
R/W 0
R/W 0
R/W 0
R/W 0
R/W 0
R/W 0
R/W 0
RO
0
RO
0
RO
0
R/W 0
R/W 0
R/W 0