241 d. i .2.P.
Digital Input 2 Process (only on ATR244-23XX-T)
Select the size related to the digital input 2.
Value read on input AI1. (Default)
A.in.1
Value read on input AI2.
A.in.2
Arithmetic average of the value read on inputs AI1 and AI2 [(AI1-AI2)/2].
MEAn
Difference of the values read on inputs AI1 and AI2 (AI1-AI2).
diFF .
Module of the difference of the values read on inputs AI1 and AI2 (|AI1-AI2|).
Ab.dif .
Sum of values read on inputs AI1 and AI2 (AI1+AI2).
SuM
242 d. i .2.r.
Digital Input 2 Reference Command
Defines the resting contact of the digital input 2.
Command 1 (Default)
cmd. 1
Command 2
cmd. 2
Command 1 and 2
cmd.1.2
243÷246
Reserved Parameters - Group N
Reserved parameters - Group N
GROUP O -
d. i . 3
247 d. i .3.f.
Digital Input 3 Function
Digital input 3 functioning.
Disabled (Default)
diSab.
2 Setpoints Switch
2t. sw.
2 Setpoints Switch Impulsive
2t.sw.i.
3 Setpoints Switch Impulsive
3t.sw.i.
4 Setpoints Switch Impulsive
4t.sw.i.
Start / Stop
st./st.
Run
rUn
Lock conversion (stop all conversions and display values)
HoLd
Performing manual tune
tune
Automatic / Manual Impulse (if enabled on parameter 48 or 67)
au.ma.i.
Automatic / Manual Contact (if enabled on parameter 48 or 67)
au.ma.c.
Action Type. Cooling regulation if D.I. is active, otherwise heating reg.
act.tY.
Analogue Input 0. Set AI to zero
A.i. 0
Manual reset. Reset the outputs if selected as manual reset.
M. reS.
Timer 1 run. The timer 1 count with activated D.I.
t.1.run
Timer 1 Start End. D.I. starts and stops the timer 1(impulsive)
t.1. s.E.
Timer 1 Start. D.I. starts the timer 1(impulsive)
t.1.Sta.
Timer 1 End. D.I. stops the timer 1(impulsive)
t.1.End
Timer 2 run. The timer 2 count with activated D.I.
t.2.run
Timer 2 Start End. D.I. starts and stops the timer 2(impulsive)
t.2. s.E.
Timer 2 Start. D.I. starts the timer 2(impulsive)
t.2.Sta.
Timer 2 End. D.I. stops the timer 2(impulsive)
t.2.End
Lock configuration and setpoints.
Lo.cfG.
Simulates the functioning of up key.
up .key
Simulates the functioning of down key.
down.k.
Simulates the functioning of fnc key.
fnc. k.
Simulates the functioning of set key.
set. k.
Remote setpoint enabling. Enables Remote setpoint with activated D.I. Local setpoint
rem.s.e.
with deactivated D.I. (remote setpoint must be enabled on parameter 56 rem.s.)
External alarm. The controller goes on STOP and the alarms will be disabled. The
ext.al.
controller does not return to START automatically: for this operation, the user's
intervention is required.
62 - ATR244 - User manual
- Digital input 3
(only on ATR244-23XX-T)