GROUP B -
A. i n.2
18
Sensor AI2
SEN.2
Analogue input configuration / sensor AI2 selection
Disabled
diSab.
Tc-K
tc. k
Tc-S
tc. s
Tc-R
tc. r
Tc-J
tc. J
Tc-T
Tc. T
Tc-E
tc. E
Tc-N
tc. N
Tc-B
tc. b
Pt100
Pt100
Ni100
ni100
NTC 10K β3435K
ntc 1
PTC 1K
Ptc
Pt500
Pt500
Pt1000
Pt1k
0..1 V
0-1
0..5 V
0-5
0..10 V
0-10
0..20 mA
0-20
4..20 mA
4-20
0..60 mV
0-60
PPotentiometer (set the value on parameter 23)
Pot.
Ni120
ni120
NTC 10K β3694K
ntc 2
NTC 2252 β3976K
ntc 3
19
Decimal Point 2
d.P. 2
Select number of displayed decimal points for AI 2
Default
0
1 decimal
0.0
2 decimals
0.00
3 decimals
0.000
20
Reserved
rEs.
Reserved parameter.
21
Lower Linear Input AI2
L.L. i .2
AI2 lower limit only for linear signals. Ex.: with input 4..20 mA this parameter takes value associated
to 4 mA. The value may be greater than the one entered on the next parameter.
-9999..+30000 [digit
22
Upper Linear Input AI2
u.L. i .2
AI2 upper limit only for linear signals Ex: with input 4..20 mA this parameter takes value associated
to 20 mA.The value may be lower than the one entered on the previous parameter..
-9999..+30000 [digit
23
Potentiometer Value AI2
P.vA.2
Selects the value of the potentiometer connected on AI2
1..150 kohm. Default: 10kohm
36 - ATR244 - User manual
- Analogue input 2
Disabled. (Default)
-260° C..1360° C.
-40° C..1760° C
-40° C..1760° C
-200° C..1200° C
-260° C..400° C
-260° C..980° C
-260° C..1280° C
100° C..1820° C
-200° C..600° C
-60° C..180° C
-40 °C..125 °C
-50° C..150° C
-200° C..600° C
-200° C..600° C
-60 °C..240 °C
-40 °C..150 °C
-40 °C..150 °C
] Default: 0.
1 p. 74
] Default:1000
1 p. 74
(only on ATR244-23XX-T)

Hide quick links: