Digital outputs
5.1.g
12/13 ABC 12ABC-T
23x
DO2
11
DI/O1
(PNP)
(PNP)
DO1
12
DI/O2
13
DI/O2
(PNP)
(PNP)
(PNP)
DI/O1
14
(PNP)
15
0V
15
0V
0V
Analogue output AO1
5.1.h
ATR244-12x and ATR244-13
9
AO1
V/mA
10
ATR244-23x
10
AO1
V/mA
11
Analogue output AO2 (only ATR244-23xx-T)
5.1.i
12
AO2
V/mA
13
Relay output Q1
5.1.j
3
Q1
2A 230V
4
Resistive
5
Relay output Q2 (only ATR244-12x)
5.1.k
7
Q2
2A 230V
Resistive
8
Relays output Q2 - Q3 (only on ATR244-13ABC and ATR244-23xx-T)
5.1.l
6
Q2
2A 230V
7
Resistive
Q3
8
Digital output PNP (including SSR) for command or alarm.
20
Range 12 VDC/25 mA or 24 VDC/15mA selectable by parameter 282
21
v.out.
Wire the positive control (+) of the solid state relay to the pin DO(x).
Wire the negative control (-) of the solid state relay to the pin 0V.
24
Linear output in mA or V (galvanically isolated) configurable as command,
alarm or retransmission of process-setpoint.
The selection mA or Volt for the linear output depends on the parameters
configuration.
Linear output in mA or V (galvanically isolated) configurable as command,
alarm or retransmission of process-setpoint.
The selection mA or Volt for the linear output depends on the parameters
configuration.
Capacity 2 A / 250 VAC for resistive loads.
See chart below.
Capacity 2 A / 250 VAC for resistive loads.
See chart below.
Capacity 2 A / 250 VAC for resistive loads.
See chart below.
Electrical endurance Q1, Q2 e Q3:
2 A, 250 VAC, resistive loads, 10
20/2 A, 250 VAC, cosφ = 0.3, 10
operations.
5
operations.
5
User manual - ATR244 - 15