114 m.G.t.2
Max Gap Tune 2
Selects the max. process-setpoint gap beyond which the automatic tune recalculates PID
parameters of process 2.
0-10000 [digit
1 p. 74
115 mn.p.2
Minimum Proportional Band 2
Selects the min. proportional band value selectable by the automatic tune for the P.I.D. regulation
of process 2.
0-10000 [digit
1 p. 74
116 ma.p.2
Maximum Proportional Band 2
Selects the max. proportional band 2 value selectable by the automatic tune for the P.I.D.
regulation of process 2.
0-10000 [digit
1 p. 74
117 mn. i .2
Minimum Integral Time 2
Selects the min. integral time 2 value selectable by the automatic tune for the P.I.D. regulation
of process 2.
0.0...1000.0 sec. Default: 30.0 sec.
118 o.c.L.2
Overshoot Control Level 2
The overshoot control function prevents this event during device switching on or when the
setpoint is modified. Setting a too low value the overshoot may not be fully absorbed, while with
high values the process could reach the setpoint more slowly.
Disab.
Lev. 1
Lev. 2
119÷122
Reserved Parameters - Group F
Reserved parameters - Group F
GROUP G -
AL. 1
123 AL. 1 .f.
Alarm 1 Function
Alarm 1 selection.
Disabled (Default)
diSab.
Absolute Upper Activation. Absolute referred to the process, active over
Ab.up .A.
Absolute Lower Activation. Absolute referred to the process, active under
Ab.Lo.a.
Band alarm (command setpoint ± alarm setpoint)
bAnd
Upper Deviation alarm
up .dev .
Lower Deviation alarm
Lo.dev .
Absolute Command Upper Activation. Absolute alarm referred to the command
Ab.c.u.A.
setpoint, active over
Absolute Command Lower Activation. Absolute alarm referred to the command
Ab.c.L.A.
setpoint, active under
Status alarm (active in RUN/START)
run
Cold actuator auxiliary (Cold action in double loop)
cooL
Probe error. Alarm active in case of sensor rupture.
Prb.er.
Related to timer 1
tMr.1
Related to timer 2
tMr.2
Related to both timers
tMr.1.2
Remote. The alarm is enabled by the word 1235
rEM.
Digital Input 1. Active when digital input 1 is active.
d.i. 1
Digital Input 2. Active when digital input 2 is active.
d.i. 2
Digital Input 3. Active when digital input 3 is active.
d.i. 3
Digital Input 4. Active when digital input 4 is active.
d.i. 4
Heater Break Alarm and Overcurrent Alarm
H.b.A.
] (degrees.tenths for temp. sensors). Default: 2.0
] (degrees.tenths for temp. sensors). Default: 3.0
] (degrees.tenths for temp. sensors). Default: 80.0
Lev. 3
Lev. 4
Lev. 5 (Default)
- Alarm 1
Lev. 6
Lev. 7
Lev. 8
Lev. 9
Lev. 10
User manual - ATR244 - 47