Frequency Converter - salmson CC HVAC Instrucciones De Instalación Y Funcionamiento

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

ENGLISH
Menu
Display
No.
visible to
Users 1 and above:
Call-up
Users 2 and above:
by:
Service:
4.3.4.1
Number of pumps
4.3.4.2
Pump alteration
4.3.4.3
Pump test run
4.3.5

Frequency converter

4.3.5.1
FC parameters
Description
*
**
***
*
Setting the number of pumps for the instal-
lation (1...6) and establishment of opera-
tion with/without standby pump
*
Establishment of the type of pump altera-
tion (in accordance with operating hours,
at the time of switch-on pulse, cyclical)
and replacement times.
It is also possible to specify a permanent
base-load pump. The number of this
pump must be entered for the purpose.
*
Setting of the pump test run interval and
of the switch-on duration for the pump
test run.
Selection as to whether the test run should
also take place with External Off.
Possibility of the pump test by means of:
One pump is started for the switch-on
duration selected above at pressing a
key. Each further pressing of the key starts
the other pumps in sequence.
*
Call-up of the menu for setting the FC
parameters and for displaying the FC sta-
tus
*
(page 1)
Setting of the maximum and minimum
output frequency and of the ramp times
of the frequency converter
Establishment of the frequency converter
type (the drives must be switched off for
this purpose)
*
(page 2)
Setting the FC frequencies for the purpose
of avoiding controlled variable jumps with
peak load cut-ins and switch-offs
Setting of the FC frequency with which
the controlled pump is to run in the event
of sensor failure
53
Setting parameters/
functions
adjustable by
Users 1 and above:
*
Users 2 and above:
**
Service:
***
Number of pumps
**
With/without standby
**
pump
Operating hours [h]
**
Alteration cycle [min]
**
No. of the perma-
**
nently set pump
Test run interval [h]
**
Test run switch-on
**
duration [s]
With External Off
**
Test
*
none
**
f
[Hz]
**
max
f
[Hz]
**
min
t
[s]
**
Ramp+
t
[s]
**
Ramp-
FC Type
***
f
[Hz]
**
Peak+
f
[Hz]
**
Peak-
f
[Hz]
**
Emer
Factory
setting
installation-
specific
installation-
specific
24
360
0
6
10
no
-
-
50
20
5
5
installation-
specific
20
50
40
Tabla de contenido
loading

Tabla de contenido