Scope Of Delivery; System - salmson CC HVAC Instrucciones De Instalación Y Funcionamiento

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

ENGLISH
The operation and setting up of the switchgear parameters is
protected by a three-stage security system. After the corre-
sponding password (Menu 4.4.1 or 4.4.2) has been entered,
the system is enabled at the associated user level (display by
means of the indicators located next to the levels designa-
tions). By pressing the login button takes the user into the sys-
tem.
User 1:
At this level (typically: local users, e.g. building superintend-
ents) the display is enabled for almost all menu items. Parame-
ter inputs are limited.
The password (4 digits; numerical) for this user level can be
assigned in Menu 4.4.1 (works setting: 1111).
User 2:
At this level (typically: operators) the display is enabled for
almost all menu items with the exception of the simulation
mode. Almost completely unlimited parameter inputs are pos-
sible.
The password (4 digits; numerical) for this user level can be
assigned in Menu 4.4.2 (works setting: 2222).
The service user level is reserved for SALMSON after-sales serv-
ice.

6.3 Scope of delivery

•Switchgear SALMSON CC-HVAC
•Wiring diagram
•Installation and operating instructions
6.4 Options/accessories
The CC system can be equipped with the options listed below.
They must be ordered separately.
Option
Battery-backed
power supply unit
buffer times on
request
PTC evaluation
relay
Individual operation
and fault signal
Low-water signal
Alarm inputs
(digital). 1...n
Ext.Quit.
SL ZU/AB
PT
H/0/A switching
Repair switch input
Bus linkup
Communication
Temperature
measurement
Remote setpoint
adjustment
0/2-10 V
Manual control
mode 0/2-10 V
Redundant sensor
Soft starter
40
Description
SPS power supply remains in the
event of mains voltage failure
Excess temperature monitoring of
pumps with PTC resistances.
Potential-free contacts for signal-
ling the pump status
Potential-free contact for signal-
ling dry running
Digital inputs for additional alarm
statuses for program linkages or
output via SPS
Digital input for remote confirma-
tion via potential-free NO contact
Digital inputs for switching peak-
load pumps ON/OFF via potential-
free NO contacts
Digital input for forced pump alter-
ation via potential-free NO con-
tact
Conversion of external H/0/A
switches via potential-free con-
tacts
Signal input for evaluation of the
auxiliary contact of a repair switch
Modules for linkage to different bus
systems (e.g. CAN-Bus, Profibus,
Modbus RTU, Ethernet, LON)
Module for remote diagnosis/
maintenance (analog modem,
GSM modem, web server)
Modules for connecting tempera-
ture sensors (see also 6.1.2)
Module for remote adjustment of
the setpoint by voltage signal
(0/2-10 V)
Module for FC frequency adjust-
ment (manual control mode) by
voltage signal (0/2-10 V)
Module for the connection of a
2. pressure/differential pressure
sensor (redundancy)
≥ 5.5 kW, the
For devices with P
2
start of the fixed speed pumps is
accomplished with soft starter
devices