Sensor (Measurement Range; Behaviour In The Event Of A Fault) - salmson CC HVAC Instrucciones De Instalación Y Funcionamiento

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

ENGLISH
Table 1, Fault signals
Code
Alarm text
E082
FC error
E040
Sensor disrupted
E060
Output pressure Max
E061
Output pressure Min
E062
Low water
E064
Frost protection
E080.1
Pump1 Alarm
E080.2
Pump2 Alarm
E080.3
Pump3 Alarm
E080.4
Pump4 Alarm
E080.5
Pump5 Alarm
E080.6
Pump6 Alarm
E100
Battery error
If the operating fault cannot be rectified, please consult the SALMSON Service Department or a SALMSON representative.
Subject to changes without prior notice
Causes
Frequency converter has signalled
faults
Electrical connection disrupted
Motor protection of the frequency
converter has tripped (e.g. short-
circuit of the FC mains power
cable; overload of the connected
pump)
Pressure sensor defective
No electrical connection to the
sensor
The output pressure of the system
has increased to above the value
set in Menu 4.3.2.2 (e.g. due to
control fault)
The output pressure of the system
has dropped below the value set
in Menu 4.3.2.2 (e.g. due to pipe
breakage)
Protection against low-water level
has triggered
Frost protection thermostat has
responded
Thermal winding excess tempera-
ture (WSK/PTC)
Motor protection has tripped
(excess current or short-circuit in
the supply line)
The battery charge has fallen
down to the minimum level; no fur-
ther buffering of the real time clock
is ensured
46
Remedy
Read faults in Menu 4.3.5 or at the
frequency converter and react in
accordance with the FC installa-
tion and operating instructions
Check connection to the fre-
quency converter and repair as
needed
Check mains power cable and
repair as needed; check pump (in
accordance with Installation and
operating instructions for the
pump)
Replace sensor
Repair electrical connection
Check controller function
Check installation
Check whether the default value is
appropriate to local conditions
Check pipe and repair as needed
Check inlet/break tank; installation
starts up again automatically
Check outside air temperature
Clean cooling fins; motors are
designed for an ambient tempera-
ture of +40°C (see also Installation
and operating instructions for the
pump)
Check pump (in accordance with
Installation and operating instruc-
tions for the pump) and supply line
Replace battery (see Section 9)