Regular Inspection And Maintenance; Daily Inspections; Weekly Inspections - ACO Lipujet-P-OAP Instrucciones De Empleo

Separador de grasa
Ocultar thumbs Ver también para Lipujet-P-OAP:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 132
Grease Separator

Regular Inspection and Maintenance

5 Regular Inspection and Maintenance
ACO recommends that you conclude a maintenance contract. This guarantees that mainte-
nance work is carried out professionally and completed in good time by ACO product specia-
lists,
section 1.1 "ACO Service".
Qualifications required for inspection and maintenance,
Persons".
Enter inspections, maintenance work and test results in the operating log book:
Inspections carried out by the operator
Taking samples
Measurement: water consumption, thickness of sludge and grease layers, pH reading,
temperature
Maintenances and general inspections
Disposals (emptying and cleaning)
NOTICE If inspections identify faults, the grease separator may only be put into operation
again when they have been rectified.

5.1 Daily Inspections

Checks carried out by the operator:
Check the grease separator for external damage.
Remove dirt in the intake pipe grit collector.

5.2 Weekly Inspections

Checks carried out by the operator:
Check the grease separator, connections, and mechanical and electrical components for
external damage.
Check the volume of sludge in the sludge trap and the thickness of the grease layer.
Remove coarse floating matter from the surface of the water.
For grease separators with a filling unit: Check the hydraulic seal in the odour
62
section 1.5 "Qualification of
trap.
Tabla de contenido
loading

Este manual también es adecuado para:

Lipujet-p-rapLipujet-s-oapLipujet-s-rap