PARAMETER
DESCRIPTION
NAME
READ ONLY
Exchanger type:
PG00
0 = Condenser
1 = Dry cooler
Master/Slave Control:
PG01
0 = Master
1 = Slave
READ ONLY
Type of wet resources:
0 = Dry
1 = Dry & Spray
PG02
2 = Spray System Evolution
3 = Adiabatic System
4 = EMERITUS®
5 = EMERITUS® dual power
supply
Number of condenser
PG03
circuits
READ ONLY
Liquid cooler circuits:
0 = 1 circuit, 1 probe
1 = 1 circuit, average of 2
probes (Vshape dry cooler
PG04
with Spray Evolution or
EMERITUS®)
2 = 2 circuits with
independent set-point (LT +
HT)
READ ONLY
Combined
condenser/evaporator heat
PG05
exchanger
0 = No
1 = Yes
Adjustment Priority for
Liquid Cooler 2 Circuits:
PG06
0 = Worse case
1 = circuit 1 priority
2 = circuit 2 priority
Refrigerant type:
1 = R22
2 = R134a
PH01
3 = R404a
4 = R407c
5 = R410a
6 = R507
Temperature
PH02
measurement unit
Pressure measurement
PH03
unit
Enable inlet water
temperature probe
PH08
0 = No
1 = Yes
LU1W - User Manual
PARAMETER
PAG.
NAME
PH09
9
PH10
39
PH11
PH12
9
PH13
PH14
62
PH15
PH16
61
PH17
PH18
55
PH19
61
PH20
PH21
31
55
,
PH23
21
21
PH24
19
113
DESCRIPTION
Enable temperature probe
inside electrical panel
0 = No
1 = Yes
Min full-scale value of
condensing pressure probe
Max full-scale value of
condensing pressure probe
Minimum full-scale value for
spray supply water pressure
probe
Maximum full-scale value for
spray supply water pressure
probe
READ ONLY
Minimum full-scale value for
wet resources water pH
transducer
READ ONLY
Maximum full-scale value for
wet resources water pH
transducer
READ ONLY
Minimum full-scale value for
wet resources water
conductivity transducer
READ ONLY
Maximum full-scale value for
wet resources water
conductivity transducer
Enable ambient temperature
probe
0 = No
1 = Yes
READ ONLY
Main Control Probe:
0 = NTC
1 = 4..20mA
Master control signal type:
0 = 0-10V
1 = 4..20mA
READ ONLY
Water spray pressure probe:
0 = 0-10V
1 = 4..20mA
READ ONLY
Adiabatic Pack Flow Meter
Model:
DN6 = 0; 1 = DN8; 2 = DN10;
3 = DN11; 4 = DN15; 5 =
DN20; 6 = DN25; 7 = DN32
READ ONLY
Wet resources supply water
pH probe
0 = 0-10V
1 = 4..20mA
REV.1.1 – 07/11/2017 - ENG