In these units, a high-pressure pump is commanded to supply the spray system, which is activated after a PR10 second
time from the control of the first spray valve (to consider the possible stroke time of the motorized valve, if present).
The system can acquire any alarm contact in the pump or in the dedicated control panel; when the pump alarm
occurs, the spray resource is blocked until the problem is resolved and the manual reset of the alarm (see chapter 13
ALARM). You can enable or disable the pump alarm acquisition via parameter PA02; parameter PH44 defines the
polarity of the alarm contact (N.C. set logic → contact open = alarm, closed contact = pump ok).
PARAMETER
NAME
Outdoor temperature for spray
PE12
enabling
Outdoor temp. differential for wet
PE13
resources (AP/spray) enabling
Fan speed with active spray (and
PF36
spray + AP)
First-step spray adjustment band
PR11
percent
Second-step spray adjustment
PR12
band percent
Delay between spray solenoid
PR14
valves deactivations
Delay between spray solenoid
PR15
valves activations
Time delay pump activation from
PR10
first spray valve command
Enable spray high-pressure pump
PA02
alarm
LU1W - User Manual
PF19
PF36
SP-PR03
Dry & Spray Adjustment
DESCRIPTION
Constant fans speed
PR11
PR04
DEFAULT
MIN
VALUE
VALUE
30.0
0.0
0.5
00
85.00
0.00
40.00
1.00
60.00
PR11
1
1
30
1
40
30
No
No
48
3° ramp
2° ramp
1° ramp
PR12
SP
MAX
UM
VALUE
80.0
°C
USER → OPTIMIZAT.
10.0
°C
PF20
%
USER → OPTIMIZAT.
PR12
%
USER → OPTIMIZAT.
PR13
%
USER → OPTIMIZAT.
Sec
9999
9999
Sec
sec
9999
Yes
-
REV.1.1 – 07/11/2017 - ENG
Temp.
MENU
ADVANCED →
T. OUTDOOR
ADVANCED →
REGULATION
ADVANCED →
REGULATION
ADVANCED →
REGULATION
ADVANCED →