The LU1W controller is equipped with an internal clock for executing scheduled tasks. You can change the date and
time settings in the RTC menu.
Attention: LU1W controller does not automatically switch from solar time to daylight saving time (and vice
versa).
The clock format is as follows: DD/MM/AAAA HH: MM: SS
When you enter the RTC menu, press ENTER to change the current date and time settings: UP and DOWN keys can
change the value of each field; use the LEFT and RIGHT keys or the ENTER key to move among the different fields;
press ENTER with the cursor on the Seconds field to confirm the changes or ESC to cancel.
You can get an alarm in case of RTC failure, enabling it by PA07 parameter. The RTC failure basically implies that the
scheduled activities are not executed.
PARAMETER
NAME
PA07
RTC alarm enable
MODBUS Registers
MODBUS
MODBUS
Name and Description
Register
Register
Parameter
Base 0
Base 1
CLOCK_RTC (Low)
0x04FE
1279
Date and time setting
0x04FF
1280
CLOCK_RTC (High)
PA07
0x07FD
2046
RTC alarm enable
LU1W - User Manual

14 RTC (REAL TIME CLOCK)

DESCRIPTION
Data Type and Notes
number of seconds
starting from midnight
01/01/2000
- long int divided into 2
words 16 bit
0 = disabled,
1 = enabled
- unsigned short int
DEFAULT
MIN
VALUE
VALUE
Yes
No
Default
value
-
1
105
MAX
UM
VALUE
-
Yes
Decimal
Min
Max
positions
01/01/2000
19/01/2068
00:00:00
03:14:07
0
1
REV.1.1 – 07/11/2017 - ENG