LU-VE Emeritus LU1W Manual De Usuario página 160

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

Regulation
temp.
Resource
request
(%)
Upon start of adjustment, ventilation will reach starting speed (PF21) and stay for the duration of startup time (PF22);
subsequently the modulation will start. In the case of startup time (PF22) equal to 0, the adjustment will start to
modulate from the ventilation point to the maximum value (fan speeds equal to PF19).
In units with wet resources, the neutral zone setting (0-100%) is subdivided according to parameters PR04 and PR05
and controls the relative resources:
Between 0% and PR04% of output ZN → Ventilation control
Between PR04% and PR05%/100% of output ZN → Single/First Wet Resource Control (adiabatic or spray
panels)
Between PR05% and 100% of output ZN → Second Wet Resource Control (EMERITUS® spray + adiabatic
panels)
0%
VENTILATION
LU1W - User Manual
PR08
PR03
PR03
PR08
PR07
PR06
Neutral Zone Adjustment
PR04%
1 ° Wet (AP or Spray)
Adjustment Band Subdivision
PR09
PR05%
2 ° Wet (Spray + AP)
37
time
time
100%
REV.1.1 – 07/11/2017 - ENG