On-Site Substituted Fan Addressing Procedure - LU-VE Emeritus LU1W Manual De Usuario

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

MODBUS
MODBUS
Parameter Name and
Register
Register
Description
Base 0
Base 1
0x28C9
10442
fanStatus 21
0x28CA
10443
fanStatus 22
7.1
If a fan needs replacement, follow the steps below to re-address the replaced fan:
Set the controller in standby by holding down the ESC button for 3 sec.; UNIT OFF appears on the main screen
Disconnect the panel by positioning the General Disconnect Switch QS1 to OFF, and open the magnetic-
thermal switch for the fan to be replaced
Replace the fan and reset the wiring
Power up the panel again with the General Disconnect Switch QS1 and wait for the software to load and the
main screen to appear
Press and hold ENTER for 3 sec. to access the main menu
Select the ADVANCED menu, enter the password (default: 10) and access the MODBUS menu. The cursor is
located on START
Next to number for the replaced fan the word OK does not appear
Power up the replaced fan by closing the relative magnetothermal switch
Wait for 10 seconds, then press ENTER
Wait until OK appears for the replaced fan (as much as a one-minute wait may be required)
When OK appears, the procedure is completed. Press the ESC key to return to the main screen, then press
and hold the ESC key for 3 seconds to reactivate the regulation (UNIT ON).
LU1W - User Manual
Data Type and Notes
0 = not active,
1 = active,
2 = in alarm
- unsigned short int
0 = not active,
1 = active,
2 = in alarm
- unsigned short int

On-site substituted fan addressing procedure

Default
Min
value
0
0
0
0
72
MODBUS
Decimal
Max
Register
positions
Type
255
0
input
255
0
input
REV.1.1 – 07/11/2017 - ENG