MODBUS Registers
MODBUS
MODBUS
Parameter Name and
Register
Register
Description
Base 0
Base 1
PR40
Activation/deactivation
delay of AP solenoid valves
from
activating/deactivating
first spray solenoid valve
0x0796
1943
on opposite side
PR41
Adjustment activation
delay SPRAY + AP (2° wet)
0x07A5
1958
from AP activation (1° wet)
PA08
0x07FE
2047
Enable spray pump alarm
The remaining adjustment parameters coincide with those in Section 4.5 Spray System Evolution Adjustment.
4.7.1
Summary of the adjustment phases for the EMERITUS® configuration
The following images summarize the steps in activating the various devices in the case of exchanger with adiabatic
panels, sprays and tank for the recovery of sprayed water.
If only the adiabatic panels (fig.2) are active, EVaux is open and the adiabatic panels are supplied with mains water.
Since the first spray step (fig. 3) is activated, EVaux is closed and the panels are supplied with the water collected in
the tank. This is the water that has not evaporated on the exchange surface.
The active devices and the flow of water are indicated in red.
LU1W - User Manual
Data Type and Notes
[sec]
- unsigned short int
[sec]
- unsigned short int
0 = Disabled
1 = Active, with OFF pump
and AP OFF in case of
alarm
2 = Active, with OFF pump
and AP ON from water
mains in case of alarm
- unsigned short int
51
Default
Min
Max
value
10
0
9999
60
0
9999
2
0
2
REV.1.1 – 07/11/2017 - ENG
MODBUS
Decimal
Register
positions
Type
0
holding
0
holding
0
holding