Restoring Factory Parameters And Saving/Uploading User Settings - LU-VE Emeritus LU1W Manual De Usuario

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

16 RESTORING FACTORY PARAMETERS AND SAVING/UPLOADING USER SETTINGS

Using the RESTORE command in the USER menu, the controller settings are restored to the factory default setting.
The restore of the factory settings can be launched by the MODBUS register:
MODBUS
MODBUS
Name and Description
Register
Register
Parameter
Base 0
Base 1
PH98
0x082E
2095
Restore factory settings
You can save your parameter setting on a USB key (4GB maximum recommended), after the first activation procedure
or a very good setting, to upload later or on controllers of other exchangers with the same configuration, components,
operating conditions, and adjustment software version.
To save your parameter map, insert the USB key into the controller's USB port and launch the SAVE PAR USB control
from the main menu.
The Parameter Map is saved in the main USB key directory, the file name is parapp.ucjm.
To upload it, copy the parameter map into the root of the USB key, insert the USB key into the controller's USB port,
and launch the LOAD PAR USB control from the main menu.
LU1W - User Manual
Data Type and Notes
1= launch the command to
restore the factory settings
(it return automatically to
0)
- unsigned short int
107
Default
Min
Max
value
0
0
1
REV.1.1 – 07/11/2017 - ENG
MODBUS
Decimal
Register
positions
Type
0
holding
Tabla de contenido
loading

Tabla de contenido