LU-VE Emeritus LU1W Manual De Usuario página 200

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

PARAMETER
NAME
Coil wash activation and
frequency:
PC10
0 = No (Disabled)
1 = Daily
2 = Weekly
PC11
Coil wash start time
Coil Wash Day:
0 = Sunday
PC12
1 = Monday
---
6 = Saturday
Waiting time on/off fans in coil
PC13
wash mode
Spray waiting time after switching
PC14
off fans in coil wash mode
PC15
Coil wash spray duration
Enable DI9 start coil wash
PH40
command
Logic DI9 start coil wash command
PH41
N.O. = normally open contact
N.C. = normally closed contact
MODBUS Registers
MODBUS
MODBUS
Parameter Name and
Register
Register
Description
Base 0
Base 1
PC10
Coil wash activation and
0x07EA
2027
frequency
PC11 (Low)
0x07EB
2028
Coil wash start time
0x07EC
2029
PC11 (High)
PC12
0x07ED
2030
Coil wash day
PC13
Waiting time on/off fans in
0x07EE
2031
coil wash mode
PC14
Spray waiting time after
switching off fans in coil
0x07EF
2032
wash mode
PC15
0x07F0
2033
Coil wash spray duration
LU1W - User Manual
DESCRIPTION
Data Type and Notes
0 = No (Disabled)
1 = Daily
2 = Weekly
- unsigned short int
number of seconds from
midnight
- long int divided into 2
word 16 bit
0 = Sunday
1 = Monday
---
6 = Saturday
- unsigned short int
[sec]
- unsigned short int
[sec]
- unsigned short int
[sec]
- unsigned short int
DEFAULT
MIN
VALUE
VALUE
No
No
23:00:00
0:00:00
Saturday
Sunday
60
1
30
1
60
1
No
No
N.O.
N.O.
Default
value
0
22:00:00
6
60
30
60
77
MAX
UM
VALUE
-
Weekly
23:59:59
hh: mm: ss
-
Saturday
sec
9999
sec
9999
sec
9999
Yes
-
-
N.C.
Decimal
Min
Max
positions
0
2
0:00:00
23:59:59
0
6
1
9999
1
9999
1
9999
REV.1.1 – 07/11/2017 - ENG
MENU
USER → WASHING
USER → WASHING
USER → WASHING
USER → WASHING
USER → WASHING
USER → WASHING
USER → WASHING
ADVANCED →
VARIOUS
MODBUS
Register
Type
0
holding
0
holding
0
holding
0
holding
0
holding
0
holding
Tabla de contenido
loading

Tabla de contenido