LU-VE Emeritus LU1W Manual De Usuario página 217

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

MODBUS
MODBUS
Name and Description
Register
Register
Parameter
Base 0
Base 1
PR62
Water pH control
0x079E
1951
warning threshold (high)
PR63
Water pH control block
0x079F
1952
threshold (high)
PR64
Water pH control
0x07A0
1953
warning threshold (low)
PR65
Water pH control block
0x07A1
1954
threshold (low)
PR67
Conductivity return
0x07A2
1955
differential
PR68
Water conductivity
control warning
0x07A3
1956
threshold
PR69
Water conductivity
0x07A4
1957
control block threshold
conducStatus
water conductivity alarm
0x28CC
10445
status
PHStatus
0x28CD
10446
water pH alarm status
LU1W - User Manual
Default
Data Type and Notes
value
- unsigned short int
- unsigned short int
- unsigned short int
- unsigned short int
[uS/cm]
- unsigned short int
[uS/cm]
- unsigned short int
[uS/cm]
- unsigned short int
1500
0=no alarm
1=warning
2=blocking alarm
- unsigned short int
0=no alarm
1=warning
2=blocking alarm
- unsigned short int
94
Min
Max
8.0
PH14
PH15
8.5
PH14
PH15
6.5
PH14
PH15
6.0
PH14
PH15
100
0
1000
800
PH16
PH17
PH16
PH17
-
-
-
-
-
-
REV.1.1 – 07/11/2017 - ENG
MODBUS
Decimal
Register
positions
Type
0.0
holding
0.0
holding
0.0
holding
0.0
holding
0
holding
0
holding
0
holding
0
input
0
input
Tabla de contenido
loading

Tabla de contenido