In a machine configured with a Dry & Spray system, the SPRAY page looks like this:
The following information appears: number of active ramps (number on black band top right -- ramps always activate
from upper to lower), adjustment temperature, spray system pressure and icons (in sequence):
•
Upper ramp 1 spray supply
•
Middle ramp 2 spray supply (if present)
•
Lower ramp 3 spray supply (if present)
•
High Pressure spray water pump request
•
Ramp water discharge active
•
Annual spray operation hours exceeded
The PROBES page shows the values of the analogue inputs, depending on the exchanger configuration:
•
Adjustment variables (temperatures or pressures), one to three inputs depending on the number of circuits
from which the adjustment variable is measured
•
In SLAVE mode, adjustment signal from remote master
•
Ambient temperature
•
For dry coolers and, if the relative probe is enabled, the inlet water temperature to the exchanger
•
Water flow rate to adiabatic panels (EMERITUS® and Adiabatic System machines)
•
Water supply pressure spray system (EMERITUS®, Spray Evolution, Dry & Spray machines)
•
pH and conductivity of the wet resources supply water (EMERITUS®, or where water quality control is
present)
LU1W - User Manual
/ High Pressure spray water pump alarm
/Limitation-block of spray resource for low water pressure
24
REV.1.1 – 07/11/2017 - ENG