The activation of the 4 spray nozzles occurs alternatively on the two sides, the activation of the adiabatic panels is
subordinate to it. When activating the first spray step (priority is given to the sector with the lowest operating hours),
the adiabatic panels on the opposite side are activated at the same time (with any delay adjustable at parameter
PR40). On activating the second spray ramp, on the opposite side of the first, the second adiabatic panel is activated.
From this point there will be active sprayers and adiabatic panels on both sides of the machine. As the request grows,
the 2 ramps that are still inactive will be activated in sequence.
The machines are equipped with a collecting tank to retrieve the water sprayed on the coil; the water is then reused
to wet the adiabatic panels before being wasted. If the pump in the collecting tank is in alarm (acquired by DI10
input), the controller response depends on the parameter PA08 setting:
•
no action
•
turning off the pump and closing the solenoid valves for the adiabatic panels
•
turning off the pump and supplying the adiabatic panels from water mains.
PARAMETER
NAME
Activation/deactivation delay AP
solenoid valves from
PR40
activating/deactivating first spray
solenoid valve on the opposite side
Activation delay SPRAY + AP (2°
PR41
wet) from AP activation (1° wet)
Enable wet spray pump alarm
0 = Disabled
1 = Active, with pump OFF and AP
PA08
OFF in case of alarm
2 = Active, with pump OFF and AP
ON from water mains in case of
alarm
LU1W - User Manual
Fans constant speed
PR04
PR36%
(% di PR03)
Spray Adjustment + Adiabatic Panels
DESCRIPTION
Set
50%
PR05
(% di PR03)
DEFAULT
MIN
VALUE
VALUE
10
0
60
0
2
0
50
Fans constant speed
Set 100%
PR13
PR11 PR12
SP
MAX
UM
VALUE
9999
sec
sec
9999
2
-
REV.1.1 – 07/11/2017 - ENG
PR
32
50%
PR32
4° sect.
activ.
1° sect.
activ.
Temp.
MENU
ADVANCED →
REGULATION
ADVANCED →
REGULATION
ADVANCED →
SAFETIES