LU-VE Emeritus LU1W Manual De Usuario página 134

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

I
Machine type
Digital Input
2
DI1
All
DI2
All
DI3
All
DI4
All
DI5
Dry cooler
Remote condenser
DI6
All
DI7
Type 4
Type 2,3,5,6
DI8
Type 2,3
Type 4,5,6
DI9
Type 4
Type 2,3,5,6
DI10
Type 3,4,6
Type 2,5
DI11
All
DI12
All
DI13
All
Digital Output
DO1
All
DO2
Type 2
Type 3,4,6
Type 5
2
Attention: in addition to connecting the cables to the DI, you must enable the control parameters; it is
possible to define the input polarity for each DI. See paragraph 2.2 Digital Inputs.
LU1W - User Manual
Configuration
Remote ON/OFF
Use according to control setpoint
Condensing/evaporation mode.
Silent night mode
Not used
Defrosting control
Spray/AP/tank water discharge
Not used
Enable Spray
Not used
Enable AP adiabatic panels
Not used
Wash activation control
Not used
Pump alarm
Not used
Not used
Not used
Frost protection
High Pressure Pump + UV Lamp
UV lamp
AP Pump + UV Lamp + SV.AUX
11
Type
Reference RE-W, RE-S, RE-T series of electrical
panels
24Vdc: XAP +
CONTACT: XA3 1-OUT
24Vdc: XAP +
CONTACT: XA3 2-OUT
24Vdc: XAP +
CONTACT: XA3 3-OUT
24Vdc: XAP +
CONTACT: XA3 4-OUT
24Vdc: XAP +
CONTACT: XA3 5-OUT
24Vdc: XAP +
CONTACT: XA3 6-OUT
24Vdc: XAP +
CONTACT: XA3 7-OUT
24Vdc: XAP +
CONTACT: XA3 8-OUT
24Vdc: XAP +
CONTACT: XA3 9-OUT
24Vdc: XAP +
CONTACT: XA3 10-OUT
Heater R1 (230Vac phase L2, max 3 A resistance)
Phase L2 230Vac: XA3 27-OUT (max 3 A resist.)
Phase L2 230Vac: XA3 27-OUT (max 3 A resist.)
Relay KM.P1 via XA3 27-OUT (phase L2 230Vac, max
3 A resist.)
REV.1.1 – 07/11/2017 - ENG