Connecting the degassing cable to the pump
Fig. 66: Terminal assignment Degas EcoAdd
The Degas EcoAdd is connected to the PCB using the indicated "BUS"
connection (terminals 6-9).
1.
Disconnect the pump from the supply voltage.
2.
Remove the terminal compartment cover.
3.
Connect the brown wire to terminal 6 (GND ).
4.
Connect the green wire to terminal 7 (CAN L).
5.
Connect the yellow wire to terminal 8 (CAN H).
6.
Connect the white wire to terminal 9 (24 V).
7.
Fit the terminal compartment cover.
NOTICE!
Tighten all four housing screws by hand (1 Nm)
Ensure that the seal on the terminal compartment is free from dirt to
ensure that it seals properly.
8.
Restore the power supply to the pump.