DETAIL OF BURNER WITH ATOMIZER UNIT, MODULATION SERVOMOTOR, RETURN PRESSURE
CONTROL, AIR WITH LPG OR NATURAL GAS PILOT BURNER
E
N
G
L
I
CONNECTION TO
POWER SUPPLY CIRCUIT
S
SEE 0002901120 FOR
ONE OR MORE BUR-
H
NERS
17 SAFETY GAS VALVE FOR IGNITION (PILOT) FLAME
18 MINIMUM AND MAXIMUM GAS PRESSURE SWITCH PILOT RAMP
19 PRESSURE CONTROL WITH BUILT-IN FILTER
20 NOZZLE RETURN THERMOSTAT FOR FUEL OIL VERSION ONLY
100 mbar PILOT GAS RAMP INLET
RETURN PRESSURE CONTROL
MIN = 10 + 12 bur
MAX = 18 + 20 bur
1
FILTER
2
BURNER PUMP (20-22 BAR)
3
PRESSURE GAUGE O-40 BAR
4 ATOMIZER BODY
5 RETURN NOZZLE WITHOUT PIN
6 RODS WITH CLOSING PINS
7 BY PASS HOLES
8
CLOSING SPRINGS
9
OPENING ELECTROMAGNETS
10 RETURN PRESSURE CONTROL
11 MODULATION SERVOMOTOR
12 AIR/FUEL REGULATION CONTROL DISK
13 AIR LOCKS
14 FLEXIBLE TUBE
15 IGNITION PILOT
16 MAIN GAS VALVE FOR IGNITION FLAME WITH FLOW CON-
TROL (PILOT FLAME)
10 / 32
0006080764_201006
FOR VERSION ...D
THERMOSTAT T R U
MIN = 10-12 BAR
MAX=18-20 BAR