7.2.4 Level 2 Programming (Adjustable Parameters) - Nice Ten TN2010 Instrucciones Y Advertencias Para El Instalador

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 130
entryled
Parameter
L8
Fault log list
Note: "
" represents factory settings
All parameters can be adjusted as required without any contraindications, only the "Motor force on opening" and "Motor force in closing"
may require special attention:
• Use of high force values are not recommended to compensate for the fact that the leaf has anomalous points of friction; excessive force
may impair the safety system and damage the leaf.
• If the "Motor force control" is used in support of the system for impact force reduction, after each adjustment the force measurement pro-
cedure must be performed, as envisaged by standard EN 12445.
• Wear and atmospheric conditions influence movement of the gate; force settings should be checked periodically
7.2.4) Level 2 programming (adjustable parameters)
By default the settable parameters are set as shown in Table 10 with: "
during modification procedures, as there is a maximum time interval of 10 seconds between pressing one key and another; otherwise the
system exits the procedure automatically memorising the changes made up to that time.
Table 11: To change adjustable parameters
1.
Press and hold [Set] for approx. 3s
2.
Release the key [Set] when led L1 starts to flash
3.
Press keys [▲] or [▼] to move the flashing led to the "input led" associated with the parameter to
be modified
4.
Press and hold [Set] during steps 5 and 6
5.
Wait approx. 3s after which the led associated with the current level of the parameter to be modified
will light up.
6.
Press keys [▲] or [▼] to move the led associated with the parameter value
7.
Release [Set]
8.
Wait 10s to exit the programming mode automatically after the maximum time interval
Note: Points 3 to 7 can be repeated during the same programming phase to modify other parameters
7.2.5) Level 1 programming examples (ON-OFF functions)
This example shows the sequence of operations required to change the factory setting of the functions "Automatic Closure" (L1) and "Always
Close" (L3).
Table 12: Example of Level 1 programming
1.
Press and hold [Set] for approx. 3s
2.
Release the key [Set] when led L1 starts to flash
3.
Press [Set] once to change the status of the function associated with L1
(Automatic closure) led L1 now emits long flashes
4.
Press [▼] twice to move the flashing led onto led L3
5.
Press [Set] once to change the status of the function associated with L3 (Always close) led L3 now
emits long flashes
6.
Press [Set] once to change the status of the function associated with L3 (Automatic closure) led L3 now
emits long flashes
7.
Wait 10s to exit the programming mode automatically after the maximum time interval
At the end of these operations leds L1 and L3 must remain lit to indicate that the functions "Automatic closure" and "Always Close" are enabled.
Led (level)
L1
Result of 1
manoeuvre (the most recent)
st
L2
Result of 2
nd
manoeuvre
L3
Result of 3
rd
manoeuvre
L4
Result of 4
th
manoeuvre
L5
Result of 5
th
manoeuvre
L6
Result of 6
th
manoeuvre
L7
Result of 7
th
manoeuvre
L8
Result of 8
th
manoeuvre
Value
" but can be modified at any time as described below. Take care
Description
Enables the user to check the
type of fault occurring in the
last 8 manoeuvres (see para-
graph "7.6.1 Fault log list").
Example
SET
3s
SET
L1
or
SET
or
SET
10s
Example
SET
3s
SET
L1
SET
L1
L3
SET
L3
SET
L3
10s
GB
19