PROGRAMMING PROCEDURE (Setting the programmer and the current sensor)
• Caution! The installation of both anti-derailment buffers is absolutely obligatory before starting programming.
• Make sure that the safety devices are at rest and the ECU is receiving mains power otherwise you will not be able to enter programming.
Caution: If the symbol
(after the warning lights have lashed for 10 seconds) to the completely closed position (automatic repositioning).
Dip-switch settings DS1
Sequential command TD/CH1 (DIP 1)
Dip 1 "ON"
= Sequential command "open-close"
Travel direction inversion only during closing.
Dip 1 "OFF" = Sequential command "open-block-close-block"
Automatic reclosing (DIP 2)
Dip 2 "ON"
= Automatic reclosing enabled
Dip 2 "OFF" = Automatic reclosing disabled
Pre-lashing (DIP 3)
Dip 3 "ON"
= Pre-lashing activated
Dip 3 "OFF" = Pre-lashing excluded
Warning light output (DIP 4)
Dip 4 "ON"
= Warning light output intermittent
Dip 4 "OFF" = Warning light output ixed
Indicator light (DIP 5)
Dip 5 "ON"
= Indicator light intermittent*
Dip 5 "OFF" = Indicator light ixed
* The indicator light lashes slowly during opening, rapidly during closing; remains
lit when the gate is blocked but not completely closed and is off when the gate is
completely closed.
FTCI (DIP 6)
Dip 6 "ON"
= FTCI also active when the gate is blocked
If the photocells are in alarm and the gate is blocked, no movement commands will
be accepted (even opening commands).
Dip 6 "OFF" = FTCI active only during closing
In both cases activating the FTCI safety device during the closing stage will force
travel direction inversion.
FTCI test (DIP 7)
Dip 7 "ON"
=
FTCI test enabled
Dip 7 "OFF" = FTCI test disabled
If you enable the security test you will have to connect both the transmitter and the
receiver to the controlled load output (CTRL 30 Vdc).
When the test is enable one second will pass between receiving a command and
carrying it out.
Motor installation (DIP 8)
Dip 8 "ON"
= Right-hand motor installation
Dip 8 "OFF" = Left-hand motor installation
Manual operating mode (DIP 9)
Dip 9 "ON"
= Manual mode enabled
Dip 9 "OFF" = Manual mode disabled
AUTOMATIC REPOSITIONING
If the programmer blocks due to an encoder count error
, the warning lights and indicator light will lash simultaneously for 2 seconds
reset
and will then switch off for 10 seconds.
After the programmer has been in this condition for 3 minutes it will (after pre-lashing
for 10 seconds) automatically move the gate, slowly, to the completely closed position
(2 times as in the programming procedure) in order to recover the correct position.
appears on the display after 3 minutes has passed since the programmer was powered up, the gate will start moving automatically
ON
1 2 3 4 5 6 7 8 9
ON
1 2 3 4 5 6 7 8 9
ON
1 2 3 4 5 6 7 8 9
ON
1 2 3 4 5 6 7 8 9
ON
1 2 3 4 5 6 7 8 9
ON
1 2 3 4 5 6 7 8 9
ON
1 2 3 4 5 6 7 8 9
ON
1 2 3 4 5 6 7 8 9
ON
1 2 3 4 5 6 7 8 9
or after a programmer
PRESS THE PROG BUTTON FOR MORE
THAN 4 SECONDS: THE "PAUSE" SYMBOL
WILL APPEAR INDICATING THAT YOU ARE
IN THE PAUSE PROGRAMMING MODE
ATTENTION! IF THE GATE MOVES
IN THE OPENING DIRECTION DIP
8 HAS BEEN SET INCORRECTLY.
PRESS "PROG" OR "TB" AGAIN
TO CANCEL THE PROCEDURE ,
SET DIP 8 CORRECTLY AND
REPEAT THE PROGRAMMING
PROCEDURE.
WHEN THE GATE REACHES THE COMPLETELY CLOSED POSITION IT INVERTS THE TRAVEL
DIRECTION AND AFTER MOVING FOR A FEW CENTIMETRES IT WILL CLOSE AGAIN TO
CONFIRM THE COMPLETELY CLOSED POSITION. AT THIS POINT THE OPENING MANOEUVRE
WILL START, AT LOW SPEED, SO AS TO FIND THE COMPLETELY OPEN POSITION. THEN IT WILL
OPEN AND CLOSE AGAIN STOPPING THE GATE NEAR THE END TRAVEL LIMIT SO AS TO
MEASURE THE CLOSING INERZIA. AT THIS POINT THE OPENING MANOEUVRE WILL START, AT
LOW SPEED, SO AS TO FIND THE COMPLETELY OPEN POSITION. ONCE IT HAS ARRIVED AT
THE COMPLETELY OPEN POSITION, IT INVERTS THE TRAVEL DIRECTION FOR A FEW
CENTIMETRES AND THEN CONTINUES OPENING IN ORDER TO CONFIRM THE COMPLETELY
OPEN POSITION. IT WILL NOW CLOSE AND OPEN AGAIN STOPPING THE GATE NEAR THE END
TRAVEL LIMIT SO AS TO MEASURE THE CLOSING INERZIA.
AFTER HAVING CARRIED OUT THIS MANOEUVRE THE GATE WILL CLOSE AGAIN. ONCE IT HAS
REACHED THE COMPLETELY CLOSED (2-3 CM FROM THE MECHANICAL TRAVEL BUFFER) THE
CONTROL LOGIC WILL CARRY OUT A COMPLETE OPENING AND CLOSING CYCLE IN ORDER TO
CALIBRATE THE CURRENT SENSOR.
THE OPERATION HAS NOT
SUCCEEDED. YOU WILL HAVE
TO REPEAT THE
PROGRAMMING PROCEDURE.
ATTENTION! If you change the dip settings during normal operation you will have to
memorise them. When the display is off press the "PROG" button once. The symbol
"diP" will appear on the display conirming correct memorisation.
CURRENT SENSOR
The programmer checks the electrical input to the motor, detecting any eventual
increase in effort above the normal operating limits and intervenes as an additional
safety device.
When the sensor intervenes the gate will automatically invert for 10 cm, both in the
closing as well as the opening direction, to free the obstacle it will then stop for 3 min-
utes and then continue moving in the original direction after a 10 second prelashing
period has elapsed.
At this point the programmer will function normally. To carry out automatic reposition-
ing without waiting for 3 minutes you may send a (TA, TC, TAL or TD) command to
the programmer. No commands will be accepted during repositioning but the security
devices will cut in and block all movement if they go into alarm.
• To interrupt the repositioning manoeuvre and delay it for another 3 minutes, press
the "PROG" button.
17
1...4... sec.
PRESS PROG
THE PAUSE TIME COUNT
WILL START INDICATED BY
THE "PAUSE" SYMBOL
FLASHING ON THE DISPLAY
PRESS PROG
THE PAUSE TIME COUNT
ENDS AND THE GATE CLOSES
SLOWLY IN ORDER TO FIND
THE COMPLETELY CLOSED
POSITION.
WHEN THE GATE REACHES THE
COMPLETELY CLOSED POSITION THE
PROGRAMMER SAVES THE PARAMETERS
AND QUITS THE PROGRAMMING MODE