European Directive
EU ErP Directive
2009/125/EC
■
CE Low Voltage Directive Compliance
This product is tested according to IEC/EN 61800-5-1 and complies with the CE Low Voltage Directive.
The following conditions must be satisfied for machines and devices incorporating this product to comply with
the CE Low Voltage Directive.
Area of Use
Install this product in a location with Overvoltage Category III and pollution degree 2 or less as specified in IEC/
CE 60664.
Guarding Against Debris
When you install IP20/UL Open type drives (models: 2xxxxB, 4xxxxB), use an enclosure panel that does not let
unwanted material enter the drive from above or below.
Grounding
The drive is designed to be used in T-N (grounded neutral point) networks.
When you use the drive in a grounded system where the neutral of the power supply and the protective conductor
are the common (TN-C), install overcurrent protective devices.
When you install the drive in other types of grounded systems, contact Yaskawa or your nearest sales
representative for instructions.
Wire Selection
Wire Selection on page 363
Refer to
Connect a Fuse and an RCM/RCD to the Input Side (Primary Side)
The drive circuit protection must comply with IEC/EN 61800-5-1 for protection against a short circuit and a
ground fault in the internal circuitry. Connect semiconductor protection fuses and a Residual Current Monitor/
Residual Current Device (RCM/RCD) on the input side for branch circuit protection. Refer to
and RCM/RCD (Input Side) on page
WARNING
Electrical Shock Hazard. After the drive blows a fuse or trips an RCM/RCD, do not immediately energize the
drive or operate peripheral devices. Wait for the time specified on the warning label at a minimum and make sure that all
indicators are OFF. Then check the wiring and peripheral device ratings to find the cause of the problem. If you do not know the
cause of the problem, contact Yaskawa before you energize the drive or peripheral devices. If you do not fix the problem before
you operate the drive or peripheral devices, it can cause serious injury or death.
■
EMC Directive
Drives with built-in EMC filters (models 4xxxC) were tested in accordance with European standard EN 61800-3,
and comply with the EMC Directive.
Use drives with built-in EMC filters or install external EMC filters to the drive input side to comply with the
EMC Directive.
Install a Drive to Conform to the EMC Directive
Install drive models 4xxxC with this procedure to comply with the EMC Directive when the drive is a single unit
or installed in a larger device.
1.
Install the drive on a grounded metal plate.
2.
Wire the drive and motor.
3.
Enable the internal EMC filter.
YASKAWA TOMPYEULA7002A LA700 Series Installation and Operation Instruction
Table 1.11 Other Applicable Standards
The drive meets the requirements for IE2 efficiency according to the European
regulation 2019/1781.
The losses and the efficiency class were determined in accordance with IEC 61800-9-2.
to select the correct wires for main circuit wiring.
360.
Applicable Standards
CE-compliant Fuse
1 English