Factory-Recommended Branch Circuit Protection for UL Listing
Use branch circuit protection to protect against short circuits and to maintain compliance with UL 61800-5-1.
Yaskawa recommends connecting semiconductor protection fuses on the input side for branch circuit protection.
Refer to
Table 10.4
and
WARNING
Electrical Shock Hazard. After the drive blows a fuse or trips an RCM/RCD, do not immediately energize the
drive or operate peripheral devices. Wait for the time specified on the warning label at a minimum and make sure that all
indicators are OFF. Then check the wiring and peripheral device ratings to find the cause of the problem. If you do not know the
cause of the problem, contact Yaskawa before you energize the drive or peripheral devices. If you do not fix the problem before
you operate the drive or peripheral devices, it can cause serious injury or death.
• 200 V Class
Use the fuses specified in this document to prepare the drive for use on a circuit that supplies not more than
100,000 RMS and not more than 240 Vac when there is a short circuit in the power supply.
• 400 V Class
Use the fuses specified in this document to prepare the drive for use on a circuit that supplies not more than
100,000 RMS and not more than 480 Vac when there is a short circuit in the power supply.
The built-in short circuit protection of the drive does not provide branch circuit protection. The user must provide
branch circuit protection as specified by the National Electric Code (NEC), the Canadian Electric Code, Part I
(CEC), and local codes.
Three-Phase 200 V Class
Table 10.4 Factory-Recommended Branch Circuit Protection: 200 V Class
Drive Model
2022
2031
2041
2059
2075
2094
2110
2144
2181
2225
2269
YASKAWA TOMPYEULA7002A LA700 Series Installation and Operation Instruction
Recomm. Gauge (AWG, kcmil)
U/T1
V/T2
-, +1
+3
W/T3
-
-
-
4/0 × 2P
-
-
-
1/0 × 2P
-
-
-
-
-
-
300 × 2P
300 × 2P
-
-
-
Table 10.5
for more information about recommended fuses.
Maximum Applicable Motor Output
kW (HP)
3.7 (5)
5.5 (7.5)
7.5 (10)
11 (15)
15 (20)
18.5 (25)
22 (30)
30 (40)
37 (50)
45 (60)
55 (75)
Crimp
Terminal
Terminal
Screw Size
Model
-
M10
80-10
-
M10
R100-10
-
M10
R60-10
2
M10
R38-10
-
M12
R150-12
-
M12
R150-12
1
M12
R60-12
Input Current Rating
A
18.2
26.5
35.5
51.2
69
84.4
72
97.3
119.2
144.3
175.4
10 Attachment
Crimping Tool
Insulation
Cap Model
Tool Model
Die Jaw
YF-1
TD-227, TD-
TP-080
214
YET-150-1
YF-1
TD-228, TD-
TP-100
214
YET-150-1
YF-1
TD-225, TD-
TP-060
213
YET-150-1
YF-1
TD-224, TD-
TP-038
212
YET-150-1
YF-1
TD-325, TD-
TP-150
313
YET-300-1
YF-1
TD-325, TD-
TP-150
313
YET-300-1
YF-1
TD-321, TD-
TP-060
311
YET-300-1
Semiconductor Protection Fuse
Rated Current
Manufacturer: EATON/Bussmann
FWH-80B
*1
FWH-100B
FWH-125B
FWH-150B
FWH-200B
FWH-225A
FWH-225A
*1
FWH-250A
FWH-225A
*1
FWH-250A
FWH-275A
*1
FWH-300A
FWH-275A
*1
FWH-350A
FWH-325A
*1
FWH-450A
FWH-600A
353