Siemens SIPROTEC 7SD5 Manual De Instrucciones página 139

Tabla de contenido
Dir.
Parámetro
1606
T1 MULTIPOLAR
1615
T2 1POL.
1616
T2
1617A
DISP.1POL.Z2
1625
T3
1635
T4
1645
T5
1655
T1B 1POL.
1656
T1B MULTIPOL
1657
IC -> Z1B
1901
PROG. U/I
1902
T ARR. ADELANTE
1903
T ARR.NO DIRECC
1910
If>>
1911
If>
1912
Uft(I>>)
1913
Uft (I>)
1914
Uff (I>>)
1915
Uff (I>)
1916
Iphi>
7SD5 Manual
C53000-G1178-C169-1
C
Posibilidades de ajuste
0.00 .. 30.00 s; ∞
0.00 .. 30.00 s; ∞
0.00 .. 30.00 s; ∞
No
Si
0.00 .. 30.00 s; ∞
0.00 .. 30.00 s; ∞
0.00 .. 30.00 s; ∞
0.00 .. 30.00 s; ∞
0.00 .. 30.00 s; ∞
No
Si
LE:Uft/LL:Uff
LE:Uff/LL:Uff
LE:Uft/LL:Uft
LE:Uft/LL:I>>
0.00 .. 30.00 s; ∞
0.00 .. 30.00 s; ∞
1A
0.25 .. 10.00 A
5A
1.25 .. 50.00 A
1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
20 .. 70 V
20 .. 70 V
40 .. 130 V
40 .. 130 V
1A
0.10 .. 8.00 A
5A
0.50 .. 40.00 A
2.5 Protección de distancia
Preajuste
0.00 s
Tiempo retardo T1-
multipolar
0.30 s
Tiempo retardo T2-1pol.
0.30 s
Tiempo retardo T2-
multipolar
No
Disparo monopolar con
falta en Z2
0.60 s
Tiempo retardo T3
0.90 s
Tiempo retardo T4
0.90 s
Tiempo retardo T5
0.00 s
Tiempo retardo T1B-1pol.
0.00 s
Tiempo retardo T1B-
multipolar
Si
Autoriz. zona Z1B para
ciclo IC
LE:Uft/LL:Uff
Programa de arranque U/I
1.20 s
T temporización arranque
adelante
1.20 s
T temporización arranque
no direccional
1.80 A
If>>: Valor de reacción
9.00 A
0.20 A
If>: Valor de reacción
1.00 A
48 V
Uft: Valor de reacción con
If>>
48 V
Uft: Valor de reacción con
If>
80 V
Uff: Valor de reacción con
If>>
80 V
Uff: Valor de reacción con
If>
0.50 A
Iphi>: Valor de reacción
2.50 A
Explicación
139
Tabla de contenido
loading

Tabla de contenido