Line lengths and system limits

Mains line to main distribution unit
Note
i
These specifications apply when using the prescribed mains fuse provided on site (25 A).
Conductor cross-section
2.5 mm²
(solid or fine-stranded)
4 mm²
(solid or fine-stranded)
6 mm²
(solid or fine-stranded)
10 mm²
(solid only)
Table 2: Maximum line length of mains line for mains fuse provided on site (25 A)
Line between main distribution unit and external sub-distribution unit
Conductor cross-section
1.5 mm²
2.5 mm²
4 mm²
Table 3: Maximum line length between main distribution unit and external sub-distribution unit
System bus
Note
i
If the maximum line length is exceeded, the set switching modes may no longer function or it may
no longer be possible to operate the eBox system. However, the emergency lighting function is still
guaranteed.
Condition
Maximum line length for system bus between the two most
remote external devices
Maximum line length for system bus between the most remote
external device and recharging device ONLITE central eBox
BCU
Table 4: Maximum line length for the system bus
Note
i
A conductor cross-section of 0.50 mm² is additionally allowed for remote display ONLITE BRI. The
maximum line length for the system bus between recharging device ONLITE central eBox BCU and
the remote display is then just 200 m.
ONLITE central eBox, Quick commissioning 3.0 | 03.2019 | en
Maximum line length
20 m
35 m
50 m
90 m
Maximum line length
45 m
75 m
100 m
Conductor cross-section:
0.75 mm²
350 m
350 m
Line lengths and system limits
Conductor cross-section:
1.50 mm²
500 m
500 m
EN
5