Checking wiring

To check the correct wiring, measure the resistance and loop resistance on the devices in the main distribution
unit and in all external sub-distribution units. Enter the measured values in the Actual value column. Also check
for external voltages and eliminate these.
Note
i
Carry out the measurement when the eBox system is free of voltage.

Measuring resistance

·
ONLITE central eBox CPU
Resistance
L -> PE
> 1000 Ω
N -> PE
< 1000 Ω
Table 8: Resistance for ONLITE central eBox CPU (power disconnected)
·
ONLITE central eBox OCM-NDA, ONLITE central eBox OCM-NPS, ONLITE central eBox OCM-NSI
Resistance
EL1 -> EN1
> 100 Ω
EL2 -> EN2
< 100 Ω
DA1/DA2 -> L
DA1/DA2 -> PE
> 10,000 Ω
DA1/DA2 -> N
Table 9: Resistance in output circuits (power disconnected)
Measuring loop resistance
·
In the main distribution unit, above ONLITE central eBox CPU, terminal block -1X2
Note
i
w
For this measurement, short-circuit the system bus for the external device that is the furthest
away from the ONLITE central eBox BCU.
Resistance
B1 -> B2
Max. 11 Ω
Table 10: Loop resistance on system bus (power disconnected)
·
ONLITE central eBox CPU (central phase monitor, emergency stop switch)
Resistance
PD -> PD
Max. 100 Ω
EO -> EO
Table 11: Loop resistance for ONLITE central eBox CPU (power disconnected)
ONLITE central eBox, Quick commissioning 3.0 | 03.2019 | en
Description
Wiring is correct
Earth fault in eBox system
Description
Wiring is correct
Wiring error
Wiring is correct
Description
Wiring is correct
Description
Wiring is correct
Checking wiring
EN
Actual value
Actual value
Actual value
Actual value
27