PRINCIPLE DIAGRAM DISK-
ELECTRODES SETTING
MOD.
A
RINOX 190L2
5
N.B. Ignition can be improved under certain working conditions by
slightly adjusting the position of the electrodes.
After having installed the nozzle, check the correct position of the
electrodes and disk according to the following levels. It's adviseable
to check levels after every intervention on head.
N.B. To prevent damage to the support effect nozzle assembly/
disassembly tasks with the aid of a wrench and counter-
wrench.
FAN ASSEMBLY DIAGRAM
- Observe the measurements indicated in the diagram when fitting
the fan.
B
C
D
0,5-1
5-5,5
3,5-4
12 / 16
0006080951_201401
SUNTEC PUMP MOD. AT 3 45A
WITH BUILT IN FILTER
1
Solenoid blocking valve for in line cutt-off
(usually closed) 1
flame
st
2
Solenoid valve for switch-over between low and high modes
(usually open) 2
flame
nd
3
Pressure outlet
(pressure take-off for air gate hydraulic jack)
4
Low pressure regulator (1
st
5
High pressure regulator (2
nd
6
Suction
7
Return internal by-pass plug
8
Pressure outlet
(pressure gauge port and air bleed valve 1/8")
9
Vacuum gauge port 1/8"
10 Nozzle outlet
N.B. The pump is preset at a 10 bar pressure (1
18 bar (2
flame).
nd
flame)
flame)
flame) and
st