Power
CANopen
CANopen
On
Run
Error
SmartConnect
Operating manual
LED displays CAN distributor
A
B
Power On
CANopen
Run
CANopen
Error
Error
The LED display Error is not allocated.
Meaning
Component is in operation.
|
Component is configured.
|
Bootloader status, firmware
|
update is being transferred to
the component.
CAN bus fault.
|
No data exchange with other
|
CAN bus components.
The auxiliary power supply is
|
not present.
The auxiliary power supply is
|
present.
Component does not have a
|
CAN-ID (LSS mode).
LED indicator is lit
LED indicator flashes
9 Help in the event of faults
C
D
Action
No measures necessary.
|
Wait.
|
If the fault persists, repeat the
|
firmware update. If the fault still
persists, replace the device
(see Chapter 10.2, page 67).
Check the CAN cables.
|
Restart the device
|
(see Chapter 10.3, page 68).
Check and connect the
|
auxiliary voltage supply.
If the fault still persists, replace
|
the device (see Chapter 10.2,
page 67).
Wait for at least 30 minutes.
|
Perform a firmware update via
|
ControlCenter.
Check the connection between
|
the monitoring unit and the
CAN distributor.
If the fault still persists after
|
several attempts, contact the
manufacturer's service
department.